Flowline DL10-01 EchoPod Ultrasonic Level Transmitter Instruction Manual

Model: DL10-01

1. Introduzione

The Flowline DL10-01 EchoPod Ultrasonic Level Transmitter is a general-purpose, non-contact liquid level sensor designed for continuous level measurement. It provides a 4-20 mA signal output and is suitable for various applications involving corrosive, sticky, or dirty liquids. This manual provides essential information for the proper installation, operation, and maintenance of your DL10-01 EchoPod transmitter.

Flowline DL10-01 EchoPod Ultrasonic Level Transmitter

Image showing the Flowline DL10-01 EchoPod Ultrasonic Level Transmitter, a compact device with a 1-inch NPT process mount and integrated cable.

2. Prodotto finitoview

The DL10-01 EchoPod offers reliable level measurement through ultrasonic technology. Key features include:

  • Continuous Non-Contact Measurement: Measures liquid levels up to 49.2 inches (1.25 meters) without physical contact with the medium.
  • Uscita 4-20 mA: Provides a standard industrial signal for integration with control systems, supporting distances up to 1000 feet (300 meters).
  • WebCal Software Configuration: Easy setup and calibration using the free WebCal software and a USB adapter (Fob).
  • Design ottimizzato: Features a narrow 2-inch beam width and a short 2-inch dead band, making it suitable for small tanks.
  • Resistenza alla corrosione: Constructed with a PVDF transducer and a Type 6P polycarbonate enclosure, ensuring durability in corrosive environments.
  • Compensazione automatica della temperatura: Ensures accurate measurements across varying process temperatures.

The device includes a 48-inch (1.2m) 4-conductor shielded polyurethane cable for connection.

3. Configurazione e installazione

3.1 Montaggio

The DL10-01 EchoPod features a 1-inch NPT process mount. Ensure the mounting location provides a clear, unobstructed path for the ultrasonic beam to the liquid surface. Use the provided Viton gasket to ensure a proper seal during installation.

3.2 Cablaggio

The transmitter operates on a 24 VDC loop power supply. It is a two-wire device with a 4-20 mA signal output. Connect the 4-conductor shielded cable according to the wiring diagram provided in the full product documentation. Ensure proper polarity and secure connections to prevent signal interference.

3.3 Configurazione

Configuration of the DL10-01 is performed using the WebCal PC Windows software and a USB 2.0 adapter (Fob). This Fob is essential for setting parameters such as range, signal invert (4-20 mA or 20-4 mA), and signal fail-safe options (4 mA, 20 mA, 21 mA, 22 mA, or hold last). Connect the Fob to your PC and the transmitter to access the configuration interface.

The device features non-volatile memory, retaining settings even after power loss. Automatic temperature compensation is integrated to maintain measurement accuracy.

4. Istruzioni per l'uso

Once properly installed and configured, the DL10-01 EchoPod continuously emits ultrasonic pulses towards the liquid surface. The time it takes for these pulses to return is used to calculate the liquid level. This measurement is then converted into a 4-20 mA current signal, which can be read by a PLC, DCS, or other control system.

  • Uscita del segnale: The output signal directly corresponds to the measured liquid level, as configured in WebLime.
  • Modalità di sicurezza: In the event of a measurement error or loss of signal, the transmitter will output the pre-configured fail-safe current (e.g., 4 mA, 20 mA, 21 mA, 22 mA, or hold last value).
  • Monitoraggio: Regularly monitor the output signal and compare it with known liquid levels to ensure accurate operation.

5. Manutenzione

The Flowline DL10-01 EchoPod is designed for minimal maintenance due to its non-contact measurement principle and robust construction.

  • Pulizia: Periodically inspect the transducer face for any buildup of dirt, scale, or other contaminants. Clean gently with a soft cloth and mild detergent if necessary. Avoid abrasive materials that could damage the PVDF transducer.
  • Integrità dell'involucro: Ensure the Type 6P polycarbonate enclosure remains sealed and free from damage to maintain its submersible and corrosion-resistant properties.
  • Ispezione dei cavi: Check the polyurethane cable for any signs of wear, cuts, or damage. Replace if integrity is compromised.

No internal user-serviceable parts are present. Refer all repairs to qualified personnel.

6. Risoluzione Dei Problemi

This section addresses common issues you might encounter with the DL10-01 EchoPod transmitter.

6.1 Noisy or Erratic Signal

  • Causa: Environmental interference, obstructions in the beam path, or temporary software/firmware glitch.
  • Soluzione:
    1. Inspect the tank for any new obstructions or changes in the liquid surface that might interfere with the ultrasonic beam.
    2. Check for strong air currents or foam on the liquid surface.
    3. Disconnect and reconnect the power to the sensor to perform a "reboot." This can resolve temporary glitches.
    4. Verify wiring connections for looseness or corrosion.
    5. Utilizzare il WebCal software to check diagnostic information and re-calibrate if necessary.

6.2 Nessun segnale di uscita

  • Causa: No power, incorrect wiring, or sensor failure.
  • Soluzione:
    1. Verify that 24 VDC power is supplied to the transmitter.
    2. Check all wiring connections for correctness and integrity.
    3. Ensure the Fob is not connected during normal operation, as it is for configuration only.
    4. Se il problema persiste, contattare il supporto tecnico.

6.3 Configuration Issues (Fob Related)

  • Causa: Missing or faulty USB adapter (Fob), incorrect WebCal software installation, or driver issues.
  • Soluzione:
    1. Ensure you have the correct Flowline USB adapter (Fob) for configuration.
    2. Verificare che il WebCal software is correctly installed on your PC and that the necessary USB drivers are present.
    3. Try connecting the Fob to a different USB port or another computer.

7. Specifiche

Parametro Valore
Campo di misura 49.2 pollici (1.25 metri)
Precisione 0.125 pollici (3 mm)
Risoluzione 0.019 pollici (0.5 mm)
Banda morta 2 pollici (5 cm)
Spessore del telaio 2 pollici (5 cm)
Configurazione WebCal PC Windows USB 2.0 (requires Fob)
Memoria Non volatile
Volume di fornituratage 24 VDC (loop)
Consumo 0.5W
Resistenza al loop 400Ω maximum
Uscita del segnale 4-20 mA, two-wire
Signal Invert 4-20 mA o 20-4 mA
Signal Fail-Safe 4 mA, 20 mA, 21 mA, 22 mA or hold last
Temperatura di processo da 20 a 140 °F (da -7 a 60 °C)
Temperatura ambiente da -31 a 140°F (da -35 a 60°C)
Compensazione della temperatura Automatico
Pressione (MWP) 30 PSI (2 bar)
Valutazione dell'involucro Type 6P, encapsulated, corrosion resistant and submersible
Materiale di recinzione Policarbonato
Transducer Material PVDF
Tipo di cavo 4-conductor, shielded
Lunghezza del cavo 48 pollici (1.2 metri)
Process Mount 1 pollice NPT
Mount Gasket Vitone
Classificazione Scopo generale
Conformità CE, RoHS
Approvazioni cFMus
Dimensioni del prodotto 7.5 x 7 x 2.3 pollici
Peso dell'articolo 7 once

8. Garanzia e supporto

For specific warranty information regarding your Flowline DL10-01 EchoPod Ultrasonic Level Transmitter, please refer to the documentation provided at the time of purchase or contact your authorized Flowline distributor or the manufacturer directly. Warranty terms typically cover defects in materials and workmanship for a specified period.

For technical support, troubleshooting assistance beyond this manual, or inquiries about replacement parts, please contact Flowline customer service or your local distributor. Ensure you have your product model number (DL10-01) and any relevant purchase details available when seeking support.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.