1. Introduzione
This manual provides essential instructions for the safe installation, operation, and maintenance of your BEST LEDR-1 LED Emergency Light. Please read this manual thoroughly before installation and retain it for future reference. The LEDR-1 is designed to provide reliable emergency illumination during power outages, ensuring safety in commercial and residential environments.
2. Importanti istruzioni di sicurezza
ATTENZIONE: Rischio di scossa elettrica. Scollegare l'alimentazione prima dell'installazione o della manutenzione.
- Tutti gli interventi di manutenzione devono essere eseguiti esclusivamente da personale qualificato.
- Non montare vicino a stufe a gas o elettriche.
- Ensure the electrical wiring is properly grounded.
- Do not use outdoors. This unit is designed for indoor use only.
- Non lasciare che i cavi di alimentazione tocchino superfici calde.
- Mount the unit in locations and at heights where it will not be subjected to tamputilizzo da parte di personale non autorizzato.
- L'uso di apparecchiature accessorie non raccomandate dal produttore può causare condizioni di pericolo.
- Non utilizzare questa apparecchiatura per scopi diversi da quelli per cui è stata concepita.
- Allow battery to charge for a minimum of 24 hours after installation before testing.
3. Contenuto della confezione
Verificare che tutti i componenti siano presenti e integri all'apertura della confezione:
- BEST LEDR-1 LED Emergency Light Fixture (1 unit)
- Hardware di montaggio (viti, tasselli)
- Dadi a filo
- Manuale dell'utente (questo documento)
- AA NiCAD Battery (pre-installed or included separately)
4. Prodotto finitoview
The BEST LEDR-1 is a compact and efficient LED emergency light designed for wall-mount applications. It features a durable white thermoplastic housing and two adjustable LED lamp heads, providing 98 lumens of bright, white light (5000 Kelvin) during emergency situations. The unit operates on 120 Volts AC and includes a rechargeable NiCAD battery for backup power.

Figura 1: Fronte view of the BEST LEDR-1 Emergency Light. This image shows the compact white thermoplastic housing with two adjustable LED lamp teste.
Caratteristiche principali:
- Alloggiamento: White Thermoplastic
- Sorgente luminosa: 2 LED heads
- Voltage: 120 Volt CA
- Batteria: NiCAD, 90 minutes average life
- Potenza luminosa: 98 lumen
- Dimensioni: Approximately 14.75" L x 3.75" W x 3.75" H
5. Installazione
The LEDR-1 is designed for flush wall mounting. Follow these steps for proper installation:
- Disconnessione dell'alimentazione: Before beginning any installation, ensure that the main power supply to the circuit where the emergency light will be installed is turned OFF at the circuit breaker or fuse box.
- Posizione di montaggio: Select a suitable wall location for mounting. The unit should be mounted at a height and in a position that allows for optimal light distribution during an emergency. Ensure the mounting surface is solid and can support the fixture's weight.
- Preparare la superficie di montaggio: Use the provided mounting hardware (screws and anchors) to secure the mounting plate or backplate of the emergency light to the wall. If the unit has a separate mounting plate, attach it first.
- Collegamenti elettrici:
- Collegare il filo nero from the emergency light to the hot (live) wire from the building's electrical supply.
- Collegare il filo bianco from the emergency light to the filo neutro from the building's electrical supply.
- Collegare il filo verde from the emergency light to the filo di terra from the building's electrical supply.
- Use the provided wire nuts to secure all connections. Ensure all connections are tight and properly insulated.
- Collegamento della batteria: If the battery is not pre-connected, connect the battery pack to the circuit board. Ensure correct polarity.
- Dispositivo sicuro: Carefully tuck all wires into the junction box or fixture housing. Secure the emergency light fixture to the mounting plate or wall according to the specific design of the unit.
- Ripristina alimentazione: Once the installation is complete and all connections are secure, restore power to the circuit. The CHARGE INDICATOR light on the unit should illuminate, indicating that the battery is charging.
- Carica iniziale: Allow the battery to charge for a minimum of 24 hours before performing the first test.
6. Funzionamento
The BEST LEDR-1 Emergency Light operates automatically:
- Accensione CA: When AC power is supplied to the unit, the charge indicator light will be ON, and the battery will be charging. The LED lamp heads will remain OFF.
- potere fuoritage: In the event of an AC power failure, the emergency light will automatically switch to battery backup mode, and the LED lamp heads will illuminate. The unit will provide emergency lighting for approximately 90 minutes.
- AC Power Restored: When AC power is restored, the LED lamp heads will turn OFF, and the unit will revert to charging the battery.
- Pulsante di prova: A test button is located on the unit. Pressing this button simulates an AC power failure, allowing you to verify that the emergency lights function correctly. Release the button to return to normal operation.
- L regolabileamp Teste: I due LED lamp heads can be manually adjusted to direct light to desired areas.
7. Manutenzione
Regular maintenance ensures the longevity and reliability of your emergency light.
Test della batteria:
Perform the following tests according to local codes and regulations (typically monthly and annually):
- Test mensile: Press and hold the test button for at least 30 seconds. The LED lamp heads should illuminate. Release the button; the lights should turn off, and the charge indicator should be ON.
- Test annuale: Disconnect AC power to the unit for a full 90 minutes. The LED lamp heads should remain illuminated for the entire duration. Reconnect AC power; the lights should turn off, and the charge indicator should be ON. If the unit fails to operate for the full 90 minutes, the battery may need replacement.
Pulizia:
Clean the exterior of the unit and lamp heads periodically with a soft, damp panno. Non usare detergenti abrasivi o solventi.
Sostituzione della batteria:
The NiCAD battery has a limited lifespan. If the unit fails the annual 90-minute test, the battery likely needs replacement. Contact a qualified electrician or the manufacturer for battery replacement instructions and compatible battery types.
8. Risoluzione Dei Problemi
| Problema | Possibile causa | Soluzione |
|---|---|---|
| Emergency lights do not turn ON during power outage or when test button is pressed. |
|
|
| Charge indicator light is OFF when AC power is present. |
|
|
| Emergency lights do not stay ON for 90 minutes during annual test. |
|
|
9. Specifiche
| Caratteristica | Dettaglio |
|---|---|
| Numero di modello | LEDR-1 |
| Marca | MIGLIORE |
| Materiale dell'alloggiamento | White Thermoplastic |
| Tipo di sorgente luminosa | LED (2 heads) |
| Voltage | 120 Volt CA |
| Cosatage | 2 watt |
| Luminosità | 98 lumen |
| Efficienza | 49 lumen/watt |
| Temperatura del colore | 5000 gradi Celsius |
| Tipo di batteria | NiCAD (1 AA battery required, included) |
| Average Battery Life (Emergency Mode) | 90 minuti |
| Tipo di installazione | Montaggio a parete a filo |
| Uso interno/esterno | Solo al chiuso |
| Dimensioni del prodotto (L x P x A) | 14.75" x 3.75" x 3.75" |
| Peso dell'articolo | 0.01 once |
| Metodo di controllo | Remote (Test Button) |
10. Garanzia e supporto
The BEST LEDR-1 LED Emergency Light comes with a full manufacturer warranty. For specific warranty details, claims, or technical support, please refer to the warranty card included with your product or contact Best Lighting Products directly. Keep your purchase receipt as proof of purchase.
For assistance, please contact Best Lighting Products customer service.