Model: TOVPD1-80-EC

1. Introduzione

This manual provides detailed instructions for the installation, operation, and maintenance of the Tomzn TOVPD1-80-EC Adjustable Over/Under Voltage and Over Current Protection Device. This device is designed to protect electrical appliances and circuits from damage caused by voltage fluctuations and excessive current. Please read this manual thoroughly before use to ensure safe and correct operation.

2. Informazioni sulla sicurezza

  • L'installazione deve essere eseguita da un elettricista qualificato.
  • Assicurarsi che l'alimentazione sia scollegata prima dell'installazione o della manutenzione.
  • Non utilizzare il dispositivo in condizioni di umidità o con le mani bagnate.
  • Verify that the device's specifications match your electrical system requirements.
  • Tenere i bambini lontani dagli impianti elettrici.

3. Prodotto finitoview

3.1. Funzioni chiave

  • Over-volumetage protezione
  • sotto-volumetage protezione
  • Protezione da sovracorrente
  • Recupero automatico
  • Volume in tempo realetage visualizzazione
  • Real-time current display
  • Vol. regolabiletage calibration (±10%)
  • Funzione di ripristino delle impostazioni di fabbrica
  • Error inquiry function

3.2. Componenti del dispositivo

The device features a digital display for voltage and current, indicator lights for protection status, and control buttons for settings adjustment.

Tomzn TOVPD1-80-EC Over/Under Voltage and Over Current Protection Device

Figura 1: Davanti view of the Tomzn TOVPD1-80-EC protection device. Note: The image displays model TOVPD1-60-EC, but the instructions apply to the TOVPD1-80-EC model with an 80 Ampprima valutazione.

The device includes input terminals (IN) and output terminals (OUT) for electrical connections, along with a power indicator and status LEDs for over-voltage (>V), under-voltage (<V), and over-current (>A).

4. Installazione

The TOVPD1-80-EC device is designed for DIN rail mounting (35mm). Follow these steps for proper installation:

  1. Disconnessione dell'alimentazione: Before starting, ensure the main power supply to the circuit is completely disconnected to prevent electrical shock.
  2. Montaggio: Snap the device onto a standard 35mm DIN rail in your electrical panel.
  3. Cablaggio:
    • Connect the incoming live (L) and neutral (N) wires from the power source to the "IN" terminals of the device.
    • Connect the outgoing live (L) and neutral (N) wires to the load (appliances/circuit) from the "OUT" terminals of the device.
    • Assicurarsi che tutti i collegamenti siano ben saldi e sicuri.
  4. Verifica: Controllare attentamente tutti i collegamenti elettrici per verificarne la correttezza e la sicurezza.
  5. Ripristino dell'energia: Restore power to the circuit. The device will power on and display the current voltage e letture attuali.

5. Operating Instructions and Settings

Il dispositivo visualizza il volume in tempo realetage and current. Use the control buttons to adjust protection parameters.

5.1. Funzioni dei pulsanti

  • Pulsante di accensione: Turns the device ON/OFF (if applicable, or for display cycling).
  • Pulsante IMPOSTA: Enters/exits setting mode and cycles through parameters.
  • Pulsante freccia su (▲): Aumenta i valori dei parametri.
  • Pulsante freccia giù (▼): Diminuisce i valori dei parametri.

5.2. Regolazione dei parametri

Per regolare un parametro:

  1. Premere il tasto IMPOSTATO button to enter the setting mode. The first parameter will flash.
  2. Premere IMPOSTATO repeatedly to cycle through the available parameters (e.g., Over-voltage protection threshold, Under-voltage protection threshold, Over-current protection threshold, recovery delays, etc.).
  3. When the desired parameter is flashing, use the (Su) e (Down) buttons to adjust its value.
  4. After setting the value, wait a few seconds for the device to automatically save the setting and exit the setting mode, or press IMPOSTATO again to move to the next parameter.

5.3. Parameter Ranges and Default Values (for 220V/80A model)

Parametro Gamma regolabile Valore predefinito
Over-volumetage Protezione (UVP) 230V ~ 300V (OFF) 270V
Over-volumetage Recovery (UVR) 225V ~ 295V 250V
UVP Action Time Da 0.1 a 30 secondi Anni 0.5
UVP Recovery Delay Da 1 a 500 secondi Anni 30
sotto-volumetage Protezione (LVP) 140V ~ 210V (OFF) 170V
sotto-volumetage Recupero (LVR) 145V ~ 215V 190V
LVP Action Time Da 0.1 a 30 secondi Anni 0.5
LVP Recovery Delay Da 1 a 500 secondi Anni 30
Over-current Protection (OCP) 1A ~ 80A (adjustable) 40A (Note: Default may vary based on specific model variant.)
OCP Action Time Da 0.1 a 30 secondi Anni 0.5
OCP Recovery Delay Da 1 a 500 secondi Anni 30
Tempo di ritardo all'accensione Da 1 a 500 secondi Anni 10

Note: The over-current adjustment range is inferred to be up to 80A for the TOVPD1-80-EC model, although the provided description mentions 40A and 63A variants. Always refer to the specific markings on your device.

5.4. Ripristino delle impostazioni di fabbrica

To restore the device to its factory default settings, press and hold the (Down) button for more than 12 seconds. The display will indicate a reset.

5.5. Error Inquiry

To inquire about past error events, press and hold the (Up) button for more than 12 seconds. The device will display error codes or logs if available.

6. Manutenzione

  • Ispezionare regolarmente il dispositivo per verificare la presenza di eventuali segni di danni fisici o collegamenti allentati.
  • Mantenere il dispositivo pulito e privo di polvere. Per la pulizia, utilizzare un panno asciutto e morbido.
  • Non utilizzare detergenti abrasivi o solventi.
  • Garantire un'adeguata ventilazione attorno al dispositivo per evitare il surriscaldamento.

7. Risoluzione Dei Problemi

Problema Possibile causa Soluzione
Il dispositivo non si accende Nessuna alimentazione; cablaggio errato; guasto interno. Controllare l'alimentazione principale. Verificare i collegamenti elettrici. Se il problema persiste, contattare l'assistenza.
Il dispositivo scatta frequentemente Protection thresholds set too low; actual voltage/current exceeds limits. Adjust protection parameters (UVP, LVP, OCP) to appropriate levels. Check load for faults.
Il display mostra il codice di errore Internal error or specific fault detected. Refer to the error inquiry function (Section 5.5) for details. If unknown, contact support.
Device does not recover automatically Automatic recovery feature disabled or recovery delay too long. Ensure automatic recovery is enabled in settings. Check recovery delay times.

8. Specifiche

Caratteristica Valore
Numero di modello TOVPD1-80-EC
Corrente nominale 80 Ampqui
Fonte di alimentazione 220V AC 50/60Hz (Nominal)
Over-volumetage Gamma di protezione 230V ~ 300V (OFF)
sotto-volumetage Gamma di protezione 140V ~ 210V (OFF)
Intervallo di regolazione della sovracorrente 1A ~ 80A
Consumo energetico <2Settembre
Vita elettrica 100,000 volte
Tipo di installazione Montaggio su guida DIN (35 mm)
Dimensioni (L x P x A) Dimensioni: 9.3 x 7.8 x 4.5 cm
Peso 200 grammi