GEYA GPS6-VAK

GEYA GPS6-VAK Adjustable Over & Under VoltagManuale utente del dispositivo di protezione e

Model: GPS6-VAK (2P-40A-220V)

1. Introduzione

This manual provides detailed instructions for the installation, operation, and maintenance of the GEYA GPS6-VAK Adjustable Over & Under Voltage Protection Device. This device is designed to protect electrical equipment from damage caused by voltage fluctuations, offering real-time monitoring of voltage, current, and cumulative energy consumption (KWH).

2. Caratteristiche del prodotto

  • Display digitale intelligente: Clear LED display shows voltage, current, and fault status for quick and straightforward monitoring.
  • Advanced Over & Under Voltage Protezione: Equipped with factory default settings of 275V overvoltage and 175V undervoltage, ensuring device safety.
  • Parametri regolabili: Offers a factory default reset time of 30s, adjustable from 2 to 900s to suit specific needs. Overvoltage e sottovolttage thresholds are also adjustable.
  • Monitoraggio corrente: Displays real-time current values (1-80A).
  • Energy Consumption (KWH) Metering: Displays the cumulative value of electricity metering.
  • Compact Size & DIN Rail Mounting: Ultra-small size, easily integrates with 35mm DIN Rail mounting, simplifying installation and providing a secure connection.

3. Specifiche

SpecificazioneValore
Numero di modelloGPS6 Voltage / Protettore di corrente
Fornitura nominale voltageAC220V (LN)
Frequenza nominaleFrequenza 50/60 Hz
Volume nominaletage220V
Corrente nominale di funzionamento40A, 63A, 80A (This model: 40A)
Tempo di ripristino1-900s (factory default: 30s)
Sovravoltage Intervallo di impostazioneAC130-300V (factory default: 275V)
Sottovoltage Intervallo di impostazioneAC80-210V (factory default: 175V)
Voltage Isteresi5V
Voltage Precisione<1%
Sovravoltage Ritardo viaggio5s
Tipo di montaggioMontaggio su guida DIN (35 mm)
Tipo di connettoreMorsetti a vite
Materiale di contattoSilver or Copper
Tipo di contattoNormalmente aperto
Modalità di funzionamentoAutomatico
CertificazioneCE

Dimensioni del prodotto

Diagram showing the dimensions of the GEYA GPS6-VAK device.

Image: Dimensions of the GPS6-VAK device, showing a width of 38mm and height of 86mm for the front view, and a depth of 67.5mm and width of 35mm for the side view.

4. How to Choose Your Device (GPS6-VA5 vs. GPS6-VAK)

GEYA offers two main models in this series: GPS6-VA5 and GPS6-VAK. The primary difference lies in their functionality. This manual specifically covers the GPS6-VAK model.

Comparison table between GEYA GPS6-VA5 and GPS6-VAK models.

Image: A comparison chart detailing features of GPS6-VA5 (Adjustable Voltage/Current Protector) and GPS6-VAK (Adjustable Voltage/Current Protector with KWH Measuring). Key differences include KWH measuring capability (present in VAK, absent in VA5) and rated frequency ranges.

  • GPS6-VA5: Vol. regolabiletage/Current Protector.
  • GPS6-VAK: Vol. regolabiletage/Current Protector with KWH Measuring. This model includes the ability to measure and display cumulative energy consumption (KWH).

5. Configurazione e installazione

5.1 Montaggio su guida DIN

The GPS6-VAK device is designed for easy installation on a standard 35mm DIN rail. Ensure the rail is securely mounted in your electrical panel.

Image showing the GEYA device mounted on a 35mm DIN rail.

Image: The device is shown securely attached to a 35mm DIN rail, illustrating the ease of installation within an electrical enclosure.

5.2 Schema elettrico

Connect the device according to the following wiring diagram. Ensure all connections are tight and secure to prevent loose contacts and potential hazards. Always disconnect power before performing any wiring.

Wiring diagram for the GEYA GPS6-VAK device with a circuit breaker and load.

Image: A wiring diagram showing the connection of the GPS6-VAK device. The 'L' (Live) and 'N' (Neutral) inputs are connected to the power source, typically through a circuit breaker. The outputs from the device are then connected to the 'Load'.

  • Connect the incoming Live (L) and Neutral (N) wires to the respective input terminals of the device.
  • Connect the Live and Neutral wires from the device's output terminals to your electrical load.
  • It is recommended to install a circuit breaker upstream of the protection device for additional safety and circuit isolation.

6. Istruzioni per l'uso

6.1 Display digitale sopraview

The device features a large-screen color digital display that shows real-time electrical parameters.

Close-up of the GEYA GPS6-VAK digital display showing voltage, current, and KWH readings.

Immagine: Un dettaglio view of the GPS6-VAK's digital display. It shows the current voltage (e.g., 220V), current (e.g., 00.0A), and cumulative KWH (e.g., 000.0 KWH). The display also indicates the 'SET' button and navigation arrows for adjustments.

  • Voltage Visualizzazione: Mostra il volume in tempo realetage (ad esempio, 220 V).
  • Visualizzazione corrente: Shows the real-time current (e.g., 00.0A). Note: The current value may not be displayed when below 1A.
  • KWH Display: Shows the cumulative energy consumption. Note: This value may not be displayed when below 0.01 KWH.

6.2 Impostazione dei parametri

Use the 'SET' button and arrow keys (Up/Down) to navigate through the menu and adjust parameters such as overvoltage soglia, sottovoltage threshold, and reset time. Refer to the on-screen menu for specific navigation and adjustment steps.

  • Press the 'SET' button to enter the setting menu.
  • Use the Up/Down arrow buttons to select the parameter you wish to adjust.
  • Press 'SET' again to confirm your selection and enter the adjustment mode.
  • Use the Up/Down arrow buttons to change the value.
  • Press 'SET' to save the new value and exit the adjustment mode.
  • The device features an automatic reset function after voltage recovery, with a factory default of 30 seconds, adjustable from 2 to 900 seconds.

7. Manutenzione

The GEYA GPS6-VAK device requires minimal maintenance. To ensure optimal performance and longevity:

  • Regularly inspect the device and its connections for any signs of damage, loose wiring, or overheating.
  • Mantenere il dispositivo pulito e privo di polvere e umidità. Per la pulizia, utilizzare un panno asciutto e morbido.
  • Ensure proper ventilation around the device to prevent heat buildup.
  • Non tentare di aprire o riparare il dispositivo da soli. Contattare personale qualificato per l'assistenza.

8. Risoluzione Dei Problemi

If you encounter issues with your GEYA GPS6-VAK device, consider the following basic troubleshooting steps:

  • Il dispositivo non si accende: Controllare l'alimentazione principale e tutti i collegamenti elettrici. Assicurarsi che il volume di ingressotage is within the device's operating range.
  • Nessuna potenza di uscita: The device may have tripped due to overvoltage, sottovoltage, or overcurrent. Check the display for fault indicators. The device should automatically reset after the set delay once the voltage ritorna alla normalità.
  • Letture errate: Verify that the wiring is correct and secure. Ensure the device is properly calibrated (though typically factory calibrated).
  • Frequenti inciampi: Review il tuo set overvoltage e sottovolttage thresholds. They might be set too close to your normal operating voltage, causing nuisance tripping. Adjust the reset time if necessary.

If the problem persists after performing these steps, contact GEYA customer support or a qualified electrician.

9. Esempio di applicazioneamples

The GEYA GPS6-VAK is suitable for a wide range of applications, providing essential voltage and current protection in various environments.

Image showing multi-scenario applications for the GEYA voltage protector, including school, dormitory, rental house, and apartment settings.

Image: The GPS6-VAK device is depicted in various application settings such as schools, dormitories, rental houses, and apartments, highlighting its versatility for both household and commercial use.

  • Uso residenziale: Protecting household appliances and electronics from voltage fluttuazioni.
  • Commercial Buildings: Ensuring stable power for office equipment and lighting systems.
  • Istituzioni educative: Safeguarding sensitive laboratory equipment and classroom electronics.
  • Rental Properties: Providing reliable power protection for tenants.

10. Garanzia e supporto

For warranty information, technical support, or service inquiries, please refer to the official GEYA webo contattare il rivenditore autorizzato. Conservare la ricevuta d'acquisto come prova d'acquisto.

GEYA Official Websito: Visit GEYA Store on Amazon

Ask a question about this manual