Generale

  • The IPGSM-4G is a commercial fire alarm communicator that offers contact ID reporting with any Fire Alarm Control Panel (FACP) that has a built-in dialer.  This single or dual path communicator connects directly to the primary and secondary communication ports of a fire panel’s Digital Alarm Communicator  Transmitter (DACT). It offers three selectable reporting paths which include: Cellular only, IP only, or IP primary/cellular backup. All signals from the IPGSM 4G are delivered to Honeywell’s AlarmNet® Network Control Center, which routes highly encrypted Ethernet data packets via a customer provided internet connection or cellular network to the appropriate central station. The state of the art AlarmNet network control center is fully redundant and monitored 24/7.  AlarmNet has the ability to route messages using AlarmNet-I and 800 PLUS services, providing true redundancy and multi-path message delivery.
  • Alternative communication methods are critical in the marketplace due to VoIP (Voice over IP), migration from POTS (Plain Old Telephone Service) and growth of digital radio networks. The IPGSM-4G’s single path communications solution allows one technology to be used (either IP or cellular) to provide the appropriate connectivity to a central station. For added reliability, our exclusive dual path solution allows both technologies (IP and cellular) to be used together for maximum survivability or for local jurisdiction requirements that specify a dual technology system.

CARATTERISTICHE E BENEFICI

  • Saves the cost of two dedicated phone lines.
  • Single or dual path communications- (can communicate to central station using cellular technology, internet, or both.
  • Requires no change to the existing Fire Alarm Control Panel configuration. (Connects directly to the primary and secondary telephone ports of a DACT.)
  • Operates over the following communication protocols: HSPA+ (4G) HSPA (HSDPA & HSUPA) (3G), EDGE (2G GPRS) (2G).
  • Selectable reporting paths and supervision intervals to meet NFPA 72, chapter 26 requirements. (Compliant with NFPA 72 2010 and 2013 supervision requirements.)
  • Works over any type of customer provided Ethernet 10/100 based network connection (LAN or WAN), DSL modem or cable modem.
  • Data transmits over standard contact-ID protocol but is secured with the industry’s advanced encryption standard (AES 256 bit).
  • Supports both dynamic (DHCP) or Public and Private Static IP  addressing.
  • Built-In Power Supply module: On board charging circuit design accommodates back-up battery. Includes primary power and battery supervision.
  • Diagnostic LEDs : Signal strength and status indicators.
  • Reliable connection: IP and GSM connection tested every day.
  • QOS: Quality of Service diagnostics via AlarmNet conveys vital communicator information including when message was received, signal strength, and message path used.
  • 7720P Hand-held programmer for easy setup.

The IPGSM-4G is designed to operate over the most common cellular networks, including 3G and HSPA+. Its multi-GSM platform technology automatically chooses the best available cellular signal in the area based on signal strength and seamlessly self-adjusts to maintain critical life safety communication. In addition, it connects to any type of customer provided Ethernet 10/100 base network connection (LAN or WAN), DSL model or cable modem. Our selectable reporting path feature allows the radio to be configured for a single or dual path solution as well as the appropriate supervision intervals based on NFPA 72 requirements. (See diagram below for selectable paths and supervision timing intervals.)Honeywell-IPGSM-4G-Single-or-Dual-Path-Commercial-Fire-Communicator-fig-1

Funzionamento

When an event occurs, the Fire Alarm Control Panel goes off hook to dial the central station. The IPGSM-4G Dialer Capture Module detects the off-hook condition and provides the fire panel with a dial tone. When the fire panel detects the dial tone, it begins dialing the central station. After the dialing is completed, the Dialer Capture Module returns a handshake to the fire panel. The fire panel then sends the contact ID reports to the Dialer Capture Module, which in turn sends a kiss-off after the report is successfully received from the fire panel. The Dialer Capture Module sends the contact ID reports to the IPGSM communications module. When all the reports are sent, the fire panel goes on-hook. The IPGSM communications module then transmits the messages to the central station either over the GSM network or the Internet (dependent on configuration).

Facile da programmare

The IPGSM-4G communicator can be pre-programmed using the 7720P programmer to enter all central-station information. This is saved to the IPGSM-4G communicator panel memory. When the IPGSM-4G communicator is installed at the site and connected to the Internet/Intranet, it registers itself with the AlarmNet receiver.
Per la maggior parte delle installazioni, gli unici parametri richiesti sono:

  • Primary City ID (two digits) obtained from your monitoring station.
  • Primary Central Station ID (two digits) obtained from your monitoring station.
  • Primary Subscriber ID (four digits) obtained from your monitoring station.
  • Communication Module’s MAC ID, and MAC CRC number located on outside of box, and inside of the module.

All of these parameters are assigned by the monitoring station.
NOTA: Some assembly is required. See Installation and Setup Guide
#800-12454 for full details.

Fire Communicator Capability
The IPGSM-4G is compatible with fire panels that use the Contact ID communications format as described in the SIA DC-05 standard.

AlarmNet
Honeywell’s AlarmNet has been the nationwide leader in alarm communications technology since 1986. A reliable alternative for the transmission of alarm signals, our radio network provides extensive coverage in the United States and Canada. AlarmNet Network Control center processes signals from powerful servers in multiple locations equipped with 24/7 infrastructure support. The AlarmNet network consist of redundant hardware servers, hot back-up databases and generators with battery back-up at all locations to ensure continuity of service. Signals from Alarm-Net are transmitted to the central station’s receivers using multiple communications paths consisting of the Internet, radio network or toll-free POTS service.

Requisiti per l'installazione

CONFORMITÀ UL
To meet UL864/NFPA, ensure the following:

  • IPGSM-4G must be installed in accordance with NFPA (National Fire Protection Association) standards 70 and 72.
  • IPGSM-4G must be mounted in the same room and within 20 feet of the fire panel.
  • IPGSM-4G, and all equipment used for the IP connection (such as the router, hub, modem, etc.) shall be listed, must be powered from an un-switched branch circuit, and be provided with appropriate standby power.
  • IPGSM-4G must use the 7AH battery (not supplied) to provide 24-hour backup capability.

IPGSM-4G Technical Specifications

ELETTRICO
Trasformatore:

  • Primario: 120 V CA, 60 Hz, 0.5 A
  • Secondario: 18VDC, 50VA

Batteria:

  • One 12 V 7.0 AH lead-acid battery: (non fornito)
  • Corrente di carica della batteria: 1 Amp massimo
  • Battery discharge current: Standby 230mA, Active 950mA

SPECIFICHE DELL'ARMADIETTO

  • Dimensioni: 14.875″ H x 12.75″ W x 3.0″ D (37.8 cm H x 32.4 cm W x 7.6 cm D)
  • Colore: Rosso

SHIPPING SPECIFICATIONS

  • Peso: 5.3 libbre. (6.94 kg)
  • Dimensioni: 15.625″ H x 13.79″ W x 9.25″ D (39.7 cm H x 34.9 cm W x 23.9 cm D)

CAMPI DI TEMPERATURA E UMIDITÀ
This system meets NFPA requirements for operation at 0 -49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (non condensing at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system’s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F.

INFORMAZIONI SULLA LINEA DI PRODOTTI

IPGSM-4G: Internet and Digital Cellular Fire Alarm Communicator Panel. Includes red cabinet with Ademco® key and lock, wall outlet box, Dialer Capture Module, IGSM Communications Module, antenna & mounting adapter, PowerBoost1 power supply, LED display board, transformer, manual, & required screws, cables, etc.
Antenna External Hardware

  • GSM-ANT3DB: 3db gain external/remote antenna
  • WA7626-CA: SNA to N Adapter
  • 7626-50HC: 50 ft. antenna cable, low loss
  • 7626-25HC: 25 ft. antenna cable, low loss

NOTA: The GSM-ANT3DB and the WA7626-CA are both required for installing an external antenna along with the necessary cable needed (7626-50HC: 50 ft. or 7626-25HC: 25 ft.)
Altri accessori

  • 7720P: IPGSM-4G hand held programmer.
  • HPTCOVER: Plug-in transformer box for IPGSM communicator.
  • BAT-1270: Battery 12 Volts, 7 AH, sealed.

ELENCHI E APPROVAZIONI DELLE AGENZIE
The listings and approvals below apply to the basic IPGSM-4G communicator panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process.
Consultare la fabbrica per lo stato dell'elenco più recente.

  • UL: S789
  • CSFM: 7300-1645: 0199
  • FDNY: Certificato di autenticità n. 6219

Ademco® and AlarmNet® are registered trademarks of Honeywell International Inc.
Questo documento non è destinato all'uso a scopo di installazione. Cerchiamo di mantenere le informazioni sui nostri prodotti aggiornate e accurate. Non possiamo coprire tutte le applicazioni specifiche o anticipare tutti i requisiti. Tutte le specifiche sono soggette a modifiche senza preavviso.

Per maggiori informazioni
Learn more about Honeywell’s IPGSM-4G and other products available by visiting www.honeywellpower.com.
Honeywell Power Products
12 Clintonville Road
Northford, CT 06472-1610
877.HPP.POWR
www.honeywell.com
firealarmresources.com

Documenti/Risorse

Honeywell IPGSM-4G Single or Dual Path Commercial Fire Communicator [pdf] Manuale del proprietario
IPGSM-4G Single or Dual Path Commercial Fire Communicator, IPGSM-4G, Single or Dual Path Commercial Fire Communicator, Single Path Commercial Fire Communicator, Dual Path Commercial Fire Communicator, Commercial Fire Communicator, Fire Communicator

Riferimenti

Lascia un commento

L'indirizzo email non verrà pubblicato. I campi obbligatori sono contrassegnati con *