AAON WHSP-454 Controller Module

SOPRA VIEW
Caratteristiche
The WSHP-454 Module monitors the compressors on an AAON® Water Source Heat Pump unit and can disable the compressors based on low Suction Pressure, Leaving Water Temperature, and Water Proof of Flow inputs. It also utilizes a Delay Timer to prevent the compressors from turning on at the same time. The WSHP-454 Module’s water circuit configuration can be either single or dual. There are nine glycol configurations for the WSHP- 454 Module—0%-40% in increments of 5%. The glycol will automatically default to 0%. The WSHP-454 Module can be used stand-alone. The WSHP-454 Module requires a 24 VAC power connection with an appropriate VA rating.
Le caratteristiche del WSHP-454 includono:
- Monitoring suction pressure, leaving water temperature, and water proof of flow.
- Provides a delay timer to prevent compressors from turning on at the same time.
- Contains a 2×8 LCD character display and 4 buttons that allow for status display, setpoint changes, and configuration changes.
Nota: The WSHP-454 Module contains no user-serviceable parts. Contact qualified technical personnel if your module is not operating correctly.
INSTALLAZIONE E CABLAGGIO
Requisiti ambientali
- The WSHP-454 Module needs to be installed in an environment that can maintain a temperature range between -30°F and 150°F and not exceed 90% RH levels (non-condensing).
Montaggio
- Il modulo WSHP-454 è alloggiato in un contenitore di plastica. È progettato per essere montato utilizzando i 3 fori di montaggio presenti sulla base del contenitore. È importante montare il modulo in un luogo protetto da temperature estreme, alte o basse, umidità, polvere e sporcizia. Fare attenzione a non danneggiare i componenti elettronici durante il montaggio del modulo. Vedere la Figura 1 per le dimensioni del modulo (in pollici).
Alimentazione elettrica
- The WSHP-454 Module requires a 24 VAC power connection with an appropriate VA rating.
AVVERTIMENTO: Rispettare la polarità! Tutte le schede devono essere cablate GND-GND e 24 VAC-VAC. La mancata osservanza della polarità potrebbe causare
Considerazioni importanti sul cablaggio
Si prega di leggere attentamente e di applicare le seguenti informazioni durante il cablaggio del modulo WSHP-454:
- To operate the WSHP-454 Module in Stand-Alone mode, you must connect power to the 24 VAC input terminal block. Do not allow wire strands to stick out and touch adjoining terminals. This could potentially cause a short circuit.
- Tutti i cavi a 24 V CA devono essere collegati in modo che tutti i fili di terra rimangano in comune. Il mancato rispetto di questa procedura può causare danni al modulo e ai dispositivi collegati.
- Tutti i cablaggi devono essere conformi alle specifiche e ai codici elettrici locali e nazionali.
- Controllare che tutti i cavi elettrici siano ben serrati nella morsettiera. Assicurarsi che i trefoli non sporgano e non tocchino i terminali adiacenti. Verificare che tutti i trasduttori necessari per il sistema siano montati nella posizione corretta e cablati ai terminali corretti.
Cablaggio autonomo Circuito idrico singolo
- To operate the WSHP-454 Module as a stand-alone, connect the Module to a 24 VAC power connection with an appropriate VA rating. See Figure 2 for wiring.

Cablaggio autonomo Doppio circuito idrico
- To operate the WSHP-454 Module as a stand-alone, connect the Module to a 24 VAC power connection with an appropriate VA rating. See Figure 3 for wiring.

Sequenza di operazioni
Generale
The following inputs and outputs are available on the WSHP-454
Module. See Table 1 below to reference the Input/Output Map.
| Ingressi binari | |
| 1 | Abilitazione compressore A1 (BIN 1) |
| 2 | Abilitazione compressore A2 (BIN 2) |
| 3 | Abilitazione compressore B1 (BIN 3) |
| 4 | Abilitazione compressore B2 (BIN 4) |
| 5 | Reversing Valve Enable (BIN 5) |
| 6 | Sistema di tenuta stagna del flusso A (BIN 6) |
| 7 | Sistema di tenuta stagna del flusso B (BIN 7) |
| Ingressi analogici | |
| 1 | Pressione di aspirazione A1 (Pres 1) |
| 2 | Pressione di aspirazione A2 (Pres 2) |
| 3 | Pressione di aspirazione B1 (Pres 3) |
| 4 | Pressione di aspirazione B2 (Pres 4) |
| 5 | Temperatura dell'acqua in uscita Sistema A (T1) |
| 6 | Temperatura dell'acqua in uscita Sistema B (T2) |
| Uscite analogiche | |
| 1 | AOUT1* |
| 2 | AOUT2* |
| 3 | AOUT3* |
| 4 | AOUT4* |
| Nota: le uscite analogiche non sono utilizzate nelle applicazioni autonome | |
| Ingressi analogici | |
| 1 | Uscita di abilitazione del compressore A1 (RLY1) |
| 2 | Uscita di abilitazione del compressore A2 (RLY2) |
| 3 | Uscita di abilitazione del compressore B1 (RLY3) |
| 4 | Uscita di abilitazione del compressore B2 (RLY4) |
| 5 | Uscita allarme (RLY5) |
Tabella 1: WSHP-454 Module Inputs & Outputs
- The WSHP-454 Module setpoints are preset at AAON and are based on the unit’s design as well as the type of coolant being used in the water loop. See Table 2, below & Table 3, page 11 for default settings. Note: These are default settings only. The setpoints may be different based on the unit’s design and coolant being used.
| Setpoint predefiniti solo per acqua | |
| Descrizione | Codice articolo: R454B |
| ASPIRAZIONE NON SICURA | 39 psig |
| MODALITÀ DI RISCALDAMENTO A BASSA ASPIRAZIONE | 96 psig |
| MODALITÀ DI RAFFREDDAMENTO A BASSA ASPIRAZIONE | 81 psig |
| BASSO LEAVING WATER TEMP | 37ºF |
| Valori di riferimento predefiniti del glicole | |||||||||
|
Descrizione |
R454B 0%
Glicole |
R454B 5%
Glicole |
R454B 10%
Glicole |
R454B 15%
Glicole |
R454B 20%
Glicole |
R454B 25%
Glicole |
R454B 30%
Glicole |
R454B 35%
Glicole |
R454B 40%
Glicole |
| NON SICURO ASPIRAZIONE | 39 psig | 39 psig | 39 psig | 39 psig | 39 psig | 39 psig | 39 psig | 39 psig | 39 psig |
| MODALITÀ DI RISCALDAMENTO A BASSA ASPIRAZIONE | 96 psig | 89 psig | 83 psig | 78 psig | 71 psig | 62 psig | 55 psig | 47 psig | 43 psig |
| MODALITÀ DI RAFFREDDAMENTO A BASSA ASPIRAZIONE | 81 psig | 81 psig | 81 psig | 81 psig | 81 psig | 81 psig | 81 psig | 81 psig | 81 psig |
| BASSO IN PARTENZA ACQUA TEMPORANEO | 37ºF | 34ºF | 30ºF | 27ºF | 20ºF | 15ºF | 9ºF | 2ºF | 0ºF |
Tabella 3: Setpoint predefiniti impostati in fabbrica – Glicole
Comandi di input autonomi
Compressore acceso/spento
- A 24-volt signal to Binary Inputs #1-4 initiates each Compressor’s On function. The source for this signal would typically come from Y1 to Y4 calls from the thermostat.
Reversing Valve Enable On/Off
- A 24 volt signal on this input indicates the unit is in the Cooling Mode. Typically, the source for this signal is the “O” call from the thermostat.
Waterproof of Flow System On/Off
- A 24-volt signal to Binary Inputs #6-7 indicates Water Proof of Flow for each system.
Suction Pressure Analog Inputs
- Sensors from Analog Inputs #1-4 correlate with the Suction Pressure of each Compressor (250 PSI).
Leaving Water Temperature Thermistor Inputs
- T1 correlates with Compressors A1 & A2 (RLY1 and RLY2). T2 correlates with Compressors B1 & B2 (RLY3 and RLY4).
NOTA: When the term “ON” is used, it means there is 24 VAC on the appropriate Binary Input. When the term “OFF” is used, it means there is 0 VAC on the appropriate Binary Input.
Funzionamento del compressore (caldo/freddo)
Un compressore può attivarsi se si verifica quanto segue:
- There is 24 VAC applied to the appropriate Binary Input for the Compressor.
- If two compressors are enabled simultaneously, a 5 second stagsi verificherà un ritardo.
- Suction Pressure is above the Low Suction Pressure Cooling (Heating) Setpoint.
- Proof of Flow for the appropriate water loop is made
- Leaving Water Temp is above the leaving Water Safety Setpoint (Heating Only).
- A minimum of 3 minutes of time is met for the compressors.
Nota: If the WSHP-454 Module receives a signal on the Reversing Valve Enable input, it will operate using the Cooling Mode Setpoints.
Schermo LCD e tasti di navigazione
Il controller WSHP-454 consente di apportare modifiche alla configurazione, view stato, modificare i setpoint, creare modalità di forza ed eseguire la diagnostica utilizzando la tastiera accanto al display LCD. Vedere la Figura 4 e fare riferimento alla Figura 5 per le descrizioni.
Figura 4: Display LCD e tasti di navigazione
Mappa delle schermate principali
- Fare riferimento alla seguente mappa per navigare tra le schermate principali del display LCD. La prima schermata è quella dell'indirizzo. Per scorrere le altre schermate, premere il tasto pulsante.

- Press to scroll through WSHP Screens.
- Press to go to ALARM Screens.

- Press to scroll through ALARMS Screens.
- Press to scroll through STATUS SYSTEM A Screens.

- Press to scroll through SETPOINT Screens.
- Press to go to STATUS SYSTEM A Screens.

- Press to scroll through STATUS SYSTEM B Screens.
- Press to go to SETPOINT Screens.

- Press to scroll through SETPOINT Screens.
Mappa degli schermi protetti
- Fare riferimento alla seguente mappa quando si naviga attraverso gli schermi LCD protetti. Dalla schermata WSHP, premere il tasto due volte fino ad arrivare alla schermata SOFTWARE. Quindi tenere premuto il tasto per 5 secondi. Per scorrere le altre schermate, premere il pulsante pulsante.

Mappa delle schermate principali
- Fare riferimento alla seguente mappa durante la navigazione tra le schermate principali. Dalla schermata WSHP AAON, premere per scorrere le schermate.

- La modalità S/A significa che il controller è in modalità autonoma

- WATER CIRCUIT CONFIGURATION
- SINGLE (Typical for AAON Coil) or DUAL (Typical for AAON Tulsa)

- REVERSING VALVE CONFIGURATION
- OFF=COOL (No signal on reversing valve input equals cool mode)
- OFF=HEAT (No signal on reversing valve input equals heat mode)

Schermate di allarme
Fare riferimento alla seguente mappa quando viewvisualizzazione delle schermate di allarme. Queste schermate verranno visualizzate automaticamente quando sono presenti allarmi.
Gli allarmi sono i seguenti:
NESSUN ALLARME: This will be shown if there are no current alarms.
BLOCCO COMPRESSORE (1-4):
- If a circuit’s Suction Pressure falls below the Low Suction Pressure Setpoint for longer than one minute twice within a two hour window, the compressor on that circuit will be locked out. Manual reset or change of mode is required to return to normal operation.
- If the Suction Pressure falls below the Unsafe Suction Setpoint for 5 seconds, that circuit’s compressor will locked out. Power will need to be cycled to restart the unit.
- If the Leaving Water Temperature falls below setpoint, the last compressor will be locked out until the Leaving Water Temperature rises 6 degrees above setpoint.
- The Leaving Water Temperature remains below setpoint for 1 minute or falls 3 degrees below setpoint. This alarm will disable when the leaving water temperature rises 12 degrees above the setpoint.
LOW H2O: The Leaving Water Temperature has dropped below setpoint. This alarm will disable when the leaving water temperature rises 6 degrees above the setpoint.
NO PROOF OF FLOW: There is a call for a compressor and there is no Proof of Flow Input Enable for more than 3 minutes or if during Heat Pump heating, the Proof of Flow Enable is open for more than 2 seconds. This alarm will disable when Proof of Flow is enabled.
LOW SUCTION PRESSURE: The Circuit’s Suction Pressure has dropped below the Low Suction Pressure for longer than one minute. This alarm will disable ten minutes after Suction Pressure rises above the setpoint.
Schermate di stato del sistema A
- Fare riferimento alla seguente mappa quando si naviga attraverso le schermate di stato del sistema A. Dalla schermata STATO SISTEMA A, premere per scorrere le schermate.

- Le schermate di stato mostrate di seguito scorreranno automaticamente se il display LCD rimane su questa schermata per 20 secondi.

- SYSTEM A, COMPRESSOR 1
This screen displays the current status of the A1 Compressor. OFF PENDING: Compressor is off, but a request is made to be on, but the 1 minimum off time has not been met. - ON: HEAT or Cool REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow

- This screen displays the current status of the A2 Compressor. OFF
- PENDING: Compressor is off, but a request is made to be on, but the 1 minimum off time has not been met.
- ON: HEAT or Cool REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow


- SISTEMA A, LETTURA DELLA PRESSIONE DEL COMPRESSORE 1

- SYSTEM A, COMPRESSOR 2 PRESSURE READING If Single Water Confi guration, this screen will display “NOT USED.”

- USCITA ANALOGICA 2 PERCENTUALE 0 – 100%
Schermate di stato del sistema B
- Fare riferimento alla seguente mappa quando si naviga attraverso le schermate di stato del sistema B. Dalla schermata STATO SISTEMA B, premere per scorrere le schermate.

- Se il sistema B è disabilitato, verrà visualizzata la schermata sopra.

- Le schermate di stato mostrate di seguito scorreranno automaticamente se il display LCD rimane su questa schermata per 20 secondi.

- SYSTEM B, COMPRESSOR 1 This screen displays the current status of the B1 Compressor. OFF
- PENDING: Compressor is off, but a request is made to be on, but the 1 minimum off time has not been met.
- ON: HEAT or Cool REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow

- SYSTEM B, COMPRESSOR 2 This screen displays the current status of the B2 Compressor. OFF
- PENDING: Compressor is off, but a request is made to be on, but the 1 minimum off time has not been met.
- ON: HEAT or Cool REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow


- If Single Water Confi guration, this screen will display “NOT USED.”

- USCITA ANALOGICA 4 PERCENTUALE 0 – 100%
Schermate di setpoint
- Fare riferimento alla seguente mappa quando si naviga attraverso le schermate di stato dei punti di regolazione. Dalle SCHERMATE DEI PUNTI DI REGOLAZIONE, premere per scorrere le schermate.
- Nota: The following screens are Status Screens. The Setpoints can’t be changed from these screens

SETPOINT MODALITÀ RISCALDAMENTO BASSA PRESSIONE DI ASPIRAZIONE
|
Glicole % |
Punto di regolazione del calore di aspirazione basso |
Glicole % |
Punto di regolazione del calore di aspirazione basso | |
| 0% | 96 bar | 25% | 62 bar | |
| 5% | 89 bar | 30% | 55 bar | |
| 10% | 83 bar | 35% | 47 bar | |
| 15% | 78 bar | 40% | 43 bar | |
| 20% | 71 bar | |||

|
Glicole % |
Low Leaving Water Temperature Setpoint |
Glicole % |
Low Leaving Water Temperature Setpoint |
|
| 0% | 37ºF | 25% | 15ºF | |
| 5% | 34ºF | 30% | 9ºF | |
| 10% | 30ºF | 35% | 2ºF | |
| 15% | 27ºF | 40% | 0ºF | |
| 20% | 20ºF | |||
Schermate di configurazione
- Fare riferimento alla seguente mappa durante la navigazione tra le schermate di configurazione. Dalla schermata CONFIG, premere per scorrere le schermate e modificare i setpoint. Utilizzare il E tasti freccia per modificare le selezioni. Premere per salvare eventuali modifiche.

- SINGLE: One cooling tower for all compressors on this module
- DOPPIO: Due torri di raffreddamento per i compressori su questo modulo

- One cooling tower for all co.mpressors on this module
- Choose between 0,5,10,15,20,25,30,35,40 percent glycol.


- OFF=HEAT: When the reversing valve input is off, the valve will be in heat mode
- OFF=COOL: When the reversing valve input is off, the valve will be in cool mode

- Questa schermata non si applica alle unità R454-B.

- A1 / B1 (default): Select this for new current configurations.
- A1 / A2: selezionare questa opzione per configurazioni precedenti "specifiche".
Schermate diagnostiche
- Fare riferimento alla seguente mappa durante la navigazione tra le schermate diagnostiche. Dalla schermata DIAGNSTC, premere per scorrere le schermate.


Schermate di output di forza
- Refer to the following map when navigating through the Force Screens. From the FORCE OUTPUTS Screen, press <ENTER>. At the FORCE MODE ON/OFF screen, press the <UP> arrow key to turn the FORCE MODE on and press the <DOWN> arrow key to turn the FORCE MODE off. Use the <UP> and <DOWN> arrow keys to increase and decrease the percentage.

Risoluzione dei problemi
Monitoraggio di sicurezza per singolo circuito idrico
Proof of Flow
- If there is a call for a compressor and there is no Proof of Flow Input Enable:
- The module will wait up to 3 minutes to activate the Proof of Flow Alarm LED(s) which will blink the code indicating failure.
- If the compressor(s) is (are) running and contact is opened for 2 seconds during Heat Pump Heating: • Compressor(s) will be turned off.
- If the compressor(s) are running and contact is opened for 2 seconds during Cooling: • Proof of Flow Input will be ignored. • No alarm will be generated.
Low Suction Pressure Detection
- If any Circuit’s Suction Pressure falls below the Low Suction Pressure Setpoint for longer than 1 minute, then the following will occur:
- The compressor(s) on that circuit will turn off.
- Alarm LED will indicate Low Suction Pressure.
- Compressor(s) will be enabled again after 10 minutes if Suction Pressure rises above setpoint.
- If any Circuit’s Suction Pressure falls below the Low Suction Pressure Setpoint for longer than 1 minute a second time within a two hour window, then the following will occur:
- The compressor(s) on that circuit will be locked out.
- Alarm LED will indicate a Compressor Lockout.
- Manual reset or change of mode (i.e., Cool to Heat) must occur to reset back to normal operation. Unsafe Suction Pressure Detection If the Suction Pressure falls below the Unsafe Suction Setpoint for 5 seconds, the circuit’s compressor will be locked out immediately and will not be allowed to restart. You will need to reset the Power to restart the unit.
Bassa temperatura dell'acqua in uscita
Nota: This safety monitoring is only performed in the Heat Mode.
- If the Leaving Water Temperature falls below setpoint, the following will occur:
- The last compressor will turn off.
- Alarm LED will indicate Compressor Low Water Temp Shutoff
- Last compressor will be locked out until the Leaving temperature is 6 degrees above setpoint.
- 2. Se la temperatura dell'acqua in uscita rimane al di sotto del punto di regolazione per 1 minuto o scende di 3 gradi al di sotto del punto di regolazione, si verifica quanto segue:
- All compressors will deactivate.
- Alarm LED will indicate Compressor Low Water Temperature Shutoff
- All compressors will be locked out until the Leaving Temperature is 12 degrees above setpoint.
Test del sensore di temperatura
- Il seguente sensore voltage and resistance tables are provided to aid in checking sensors that appear to be operating incorrectly. Many system operating problems can be traced to incorrect sensor wiring. Be sure all sensors are wired per the wiring diagrams in this manual. If the sensors still do not appear to be operating or reading correctly, check voltage/o resistenza per confermare il corretto funzionamento del sensore secondo le tabelle. Seguire le note e le istruzioni riportate sotto ogni tabella durante il controllo dei sensori.
| Temperatura – Resistenza – Voltage per sensori a termistore di tipo III da 10 K Ohm | ||
| Temperatura (ºF) |
Resistenza (Ohm) |
Voltage @ Ingresso (VDC) |
| -10 | 93333 | 4.620 |
| -5 | 80531 | 4.550 |
| 0 | 69822 | 4.474 |
| 5 | 60552 | 4.390 |
| 10 | 52500 | 4.297 |
| 15 | 45902 | 4.200 |
| 20 | 40147 | 4.095 |
| 25 | 35165 | 3.982 |
| 30 | 30805 | 3.862 |
| 35 | 27140 | 3.737 |
| 40 | 23874 | 3.605 |
| 45 | 21094 | 3.470 |
| 50 | 18655 | 3.330 |
| 52 | 17799 | 3.275 |
| 54 | 16956 | 3.217 |
| 56 | 16164 | 3.160 |
| 58 | 15385 | 3.100 |
| 60 | 14681 | 3.042 |
| 62 | 14014 | 2.985 |
| 64 | 13382 | 2.927 |
| 66 | 12758 | 2.867 |
| 68 | 12191 | 2.810 |
| 69 | 11906 | 2.780 |
| 70 | 11652 | 2.752 |
| 71 | 11379 | 2.722 |
| 72 | 11136 | 2.695 |
| 73 | 10878 | 2.665 |
Table 5: Temperature/Resistance for Type III 10K Ohm Thermistor Sensors, continued
Istruzioni per il test del sensore termistore
- Utilizzare la colonna di resistenza per controllare il sensore del termistore mentre è scollegato dai controller (non alimentato). Utilizzare il voltage colonna per controllare i sensori mentre è collegato ai controller alimentati. Leggi vol.tage with meter set on DC volts. Place the “-” (minus) lead on the GND terminal and the “+” (plus) lead on the sensor input terminal being investigated. If the voltage è superiore a 5.08 VDC, quindi il sensore o il cablaggio è "aperto". Se il voltagSe e è inferiore a 0.05 VDC, il sensore o il cablaggio sono in cortocircuito.
Test del trasduttore di pressione di aspirazione per refrigerante R454-B
- La temperatura della serpentina dell'evaporatore viene calcolata convertendo la pressione di aspirazione in temperatura. La pressione di aspirazione si ottiene utilizzando il trasduttore di pressione di aspirazione, collegato alla linea di aspirazione del compressore.
- Usa il volumetage colonna per controllare il trasduttore di pressione di aspirazione mentre è collegato al modulo WSHP-454. Leggi voltage con un misuratore impostato su volt CC. Se la temperatura/volumetage o pressione/voltagSe le letture non corrispondono esattamente al grafico, è probabile che il trasduttore di pressione di aspirazione sia difettoso e dovrà essere sostituito.
Utilizzo dei LED per verificare il funzionamento
- The WSHP-454 Module is equipped with LEDs that can be used to verify operation and perform troubleshooting. There are LEDs for communication, operation modes, diagnostic codes, and relays. The Module has twenty LEDs—one used for power, one used for communications, one used for operation status, one used for alarms, five used for compressor relays, four used for Suction Pressure Transducer status, and seven used for Binary Input status. See Figures 6, page 24 & Figure 7, page 25 for the LED locations.
- The LEDs associated with these inputs and outputs allow you to see what is active without using a voltmeter.
Operation Status LEDs
- “STATUS” – This is the status blink code LED. It will light up and first blink the address of the Module. It will then blink out the Mode of Operation. See Table 6 below for Status Blink Code descriptions. The blink code descriptions are also located on the Module’s front cover. See Figure 6 for the location.
"ALLARME" – This is the diagnostic blink code LED. It will light up and blink out diagnostic codes. See Table 7 below for Diagnostic Blink Code descriptions. The blink code descriptions are also
located on the Module’s front cover. See Figure 6 for location
| Numero di battiti di ciglia |
Stato |
| 1 | Modalità off |
| 2 | Modalità Cool |
| 3 | Modalità calore |
Tabella 6: Codici di lampeggiamento dei LED di stato
| Numero di battiti di ciglia |
Allarmi |
| 1 | Bassa pressione di aspirazione |
| 2 | Blocco compressore |
| 3 | Water Flow Failure |
| 4 | Bassa temperatura dell'acqua in uscita |
Tabella 7: Codici di lampeggiamento dei LED di allarme
| TRASDUTTORE DI PRESSIONE DI ASPIRAZIONE
COIL PRESSURE, TEMPERATURE, AND VOLTAGE CHART FOR R454 REFRIGERANT |
|||
|
Temperatura (°F) |
Temperatura (ºC) |
Pressione (psi) |
Segnale Volt CC |
| 25.88 | -3.4 | 80.94 | 1.8 |
| 29.42 | -1.4 | 87.16 | 1.9 |
| 32.81 | 0.5 | 93.39 | 2.0 |
| 36.05 | 2.6 | 99.62 | 2.1 |
| 39.16 | 4.0 | 105.84 | 2.2 |
| 42.15 | 5.6 | 112.07 | 2.3 |
| 45.02 | 7.2 | 118.29 | 2.4 |
| 47.79 | 8.8 | 124.52 | 2.5 |
| 50.47 | 10.3 | 130.75 | 2.6 |
| 53.06 | 11.7 | 136.97 | 2.7 |
| 55.57 | 13.1 | 143.20 | 2.8 |
| 57.99 | 14.4 | 149.42 | 2.9 |
| 60.36 | 15.8 | 155.65 | 3.0 |
| 62.65 | 17.0 | 161.88 | 3.1 |
| 64.88 | 18.3 | 168.10 | 3.2 |
| 67.05 | 19.5 | 174.32 | 3.3 |
| 69.16 | 20.6 | 180.55 | 3.4 |
| 71.23 | 21.8 | 186.78 | 3.5 |
| 73.24 | 22.9 | 193.00 | 3.6 |
| 75.20 | 24.0 | 199.23 | 3.7 |
| 77.12 | 25.1 | 205.46 | 3.8 |
| 79.00 | 26.1 | 211.68 | 3.9 |
| 80.83 | 27.1 | 217.91 | 4.0 |
| 82.63 | 28.1 | 224.14 | 4.1 |
| 84.39 | 29.1 | 230.36 | 4.2 |
| 86.11 | 30.1 | 236.59 | 4.3 |
Suction Pressure Transducer LEDs
“PRES 1-4” – There are LEDs for each of the Suction Pressure Transducers. Since each compressor has a sensor, these LEDs which are located on the top left of the WSHP-454 Module will give a better indication of which compressor is causing an alarm. See Table 9 for PRES LED status descriptions. See Figure 7 for locations.
| Numero di battiti di ciglia |
Stato |
| Acceso fisso | Sensor is Detected and is OK |
| Spento fisso | Sensor is Not Detected |
| 1 | Low Suction Pressure on this Compressor |
| 2 | Il compressore è bloccato |
Tabella 9: Codici di lampeggiamento LED PRES 1-4
Diagnostica LED
- LED “POWER”: When the WSHP-454 Module is powered up, the POWER LED (located above the address switches) should light up and stay on continuously. If it does not light up, check to be sure that the power wiring is connected to the board, the connections are tight, and the controller is powered (if connected). If after making all these checks, the POWER LED does not light up, the module is probably defective.
- “LED "COMM": When the WSHP-454 Module is powered up while in Stand Alone Mode, the COMM LED does not light up.
- “STATUS” LED: As previously described, when the WSHP Module is first powered up, the STATUS LED will blink out the Mode of Operation.
- LED “ALLARME”: Come descritto in precedenza, questo LED lampeggerà e si spegnerà per indicare allarmi e diagnostica.
- NOTA: The WSHP-454 Module contains no user-serviceable parts. Contact qualified technical personnel if your Module is not operating correctly.