Eltako KR09-12V/UC

Eltako KR09-12V UC Coupling Relay User Manual

Model: KR09-12V/UC | Brand: Eltako

1. Introduzione

This manual provides essential information for the safe and efficient installation, operation, and maintenance of your Eltako KR09-12V UC Coupling Relay. Please read these instructions carefully before using the device and retain them for future reference. The Eltako KR09-12V UC is a coupling relay designed for various electrical switching applications, featuring a nominal voltage of 230V and a maximum switching current of 2A with one normally open (NO) contact.

2. Istruzioni di sicurezza

3. Prodotto finitoview

The Eltako KR09-12V UC is a compact coupling relay designed for reliable switching operations in various control circuits. It features a single normally open (NO) contact and is rated for a nominal voltage of 230V with a maximum switching current of 2A. Its screw terminals ensure secure electrical connections.

Eltako KR09-12V UC Coupling Relay

Figura 1: Eltako KR09-12V UC Coupling Relay. This image displays the compact design of the relay, highlighting its terminals and housing.

Caratteristiche principali:

4. Specifiche

CaratteristicaValore
ProduttoreEltako
Numero di modelloKR09-12V/UC
Dimensioni (L x P x A)Dimensioni: 10 x 5 x 1 cm
Peso40 grammi
Volume Nominaletage230 Volt
Bobina voltage12 Volt (CC)
Max. Corrente di commutazione2 A
Energia240 Watt
Tipo di contatto1 Normalmente Aperto (NO)
Materiale di contattoRame
Tipo di connessioneMorsetti a vite
Modalità operativaAutomatico
CertificazioneCULus, VDE
Uso previstoProfessional and Domestic Use

5. Configurazione e installazione

The Eltako KR09-12V UC coupling relay is designed for fixed installation. Due to the electrical nature of this device, installation must be carried out by a qualified electrician in accordance with all applicable national and local electrical codes and regulations.

  1. Disconnessione dell'alimentazione: Before commencing any installation work, ensure that the main power supply to the circuit is completely disconnected and secured against accidental re-connection.
  2. Montaggio: Mount the relay in a suitable enclosure or on a DIN rail, ensuring adequate ventilation and protection from environmental factors.
  3. Collegamenti elettrici: Connect the relay using the screw terminals. Refer to the wiring diagram provided with the product packaging for specific connection points. Ensure all connections are tight and secure to prevent loose contacts and potential hazards.
  4. Bobina voltage: Collegare il controllo 12V DC voltage to the relay coil terminals.
  5. Connessione di carico: Connect the load circuit to the normally open (NO) contact terminals. Ensure the load voltage and current do not exceed the relay's ratings (230V, 2A).
  6. Verifica: After wiring, double-check all connections for correctness and security.
  7. Ripristino dell'energia: Restore power to the circuit and test the relay's functionality.

Note: Incorrect installation can lead to device malfunction, electrical shock, or fire.

6. Istruzioni per l'uso

The Eltako KR09-12V UC coupling relay operates automatically based on the control signal applied to its coil. When the 12V DC coil voltage is present, the normally open (NO) contact will close, completing the load circuit. When the 12V DC coil voltage is removed, the NO contact will open, breaking the load circuit.

7. Manutenzione

The Eltako KR09-12V UC coupling relay is designed for long-term, maintenance-free operation under normal conditions. However, periodic inspection is recommended to ensure optimal performance and safety.

Note: Do not attempt to open or repair the relay yourself. Refer to qualified personnel for any repairs.

8. Risoluzione Dei Problemi

If you encounter issues with your Eltako KR09-12V UC coupling relay, consider the following common troubleshooting steps:

ProblemaPossibile causaSoluzione
Relay does not activate (contact does not close)No 12V DC coil voltage; Incorrect wiring; Faulty relay coil.Check 12V DC supply to coil terminals; Verify wiring against diagram; Replace relay if coil is faulty.
Relay activates but load does not receive powerLoad circuit wiring error; Faulty load; Overload protection tripped; Damaged relay contact.Check load circuit wiring; Test the load independently; Check circuit breakers/fuses; Replace relay if contact is damaged.
Relay remains activated (contact stays closed)Bobina voltage not removed; Contact welded shut due to overload.Ensure 12V DC coil voltage is correctly removed; Replace relay if contacts are welded.
Overheating or unusual odorsOverload; Loose connections; Internal fault.Immediately disconnect power. Check load current; Tighten all connections; Replace relay if internal fault is suspected.

If the problem persists after performing these steps, contact a qualified electrician or Eltako customer support for further assistance.

9. Garanzia e supporto

Eltako products are manufactured to high-quality standards. This product comes with a stated spare parts availability of 1 year. For specific warranty terms and conditions, please refer to the documentation provided with your purchase or visit the official Eltako websito.

For technical support, inquiries, or to report a fault, please contact your local Eltako distributor or visit the Eltako official websito per le informazioni di contatto.

Documenti correlati - KR09-12V/UC

Preview Eltako Coupling Relays KR09 Series Technical Data
Technical specifications and product details for Eltako KR09 series coupling relays, including control voltages, switching capacity, and operating conditions.
Preview Interruttore a impulsi Eltako ESR12NP-230V+UC con funzione relè integrata
Specifiche tecniche e istruzioni per l'uso del relè passo-passo Eltako ESR12NP-230V+UC con funzione relè integrata. Dettagli su installazione, funzioni, dati tecnici e cablaggio.
Preview Relè di isolamento motore Eltako MTR62-230V - Specifiche tecniche
Specifiche tecniche dettagliate e guida al collegamento per il relè di isolamento motore Eltako MTR62-230V, con 2+2 contatti NO per motori da 230 V, condizioni ambientali e avvisi operativi.
Preview Relè temporizzato multifunzione Eltako MFZ12DX-UC - Manuale utente
Guida completa al relè temporizzatore multifunzione analogico regolabile Eltako MFZ12DX-UC, che descrive in dettaglio le sue 18 funzioni, le specifiche tecniche e le modalità di collegamento.ampmeno.
Preview Eltako Produkte und Preise 2012: Schaltgeräte, Netzteile & Stromzähler für Gebäudeautomation
Der Eltako Produktkatalog 2012 bietet eine umfassende Übersicht über Schaltgeräte, Netzteile und elektronische Stromzähler für die Gebäudeinstallation und Steuerungstechnik. Entdecken Sie innovative Lösungen wie Stromstoßschalter, Dimmschalter, Zeitschalter, Relais und mehr, entwickelt mit Fokus auf Energieeffizienz und Langlebigkeit.
Preview Eltako TLZ12G-230V+UC Staircase Time Switch Technical Data
Technical specifications, functions, and connection diagrams for the Eltako TLZ12G-230V+UC staircase time switch. Features include switch-off early warning, pushbutton permanent light, ESL optimization, and a 400W switching capacity.