The Leviton 2761 is an industrial-grade, non-grounding locking plug designed for demanding electrical applications. This 30 Amp, 277/480 Volt 3PY, NEMA L19-30P plug features a 4-pole, 4-wire configuration, ensuring secure and reliable power connections. Constructed with a Super Tough Nylon body and solid brass blades/contacts, it offers durability and performance.

Leviton 2761 30 Amp NEMA L19-30P Locking Plug

Image: Leviton 2761 30 Amp NEMA L19-30P Locking Plug, showcasing its black and white body with brass pins.

Informazioni sulla sicurezza

ATTENZIONE: Pericolo di scossa. To avoid risk of serious injury or death, always turn power off at the circuit breaker before wiring any electrical device. Ensure all connections are secure and comply with local electrical codes. If you are unsure about any step, consult a qualified electrician.

Specifiche

Numero di modello2761
Amprabbia30 Amps
Voltage Valutazione277/480 Volt 3PY
Configurazione NEMAL19-30P
Poli/fili4 poli, 4 fili
Tipo di messa a terraNon-messa a terra
MaterialeSuper Tough Nylon (Body), Solid Brass (Blade/Contact)
ColoreBianco-Nero
ApprovazioniUL 498, CSA C22.2, NOM 057

Istruzioni per l'installazione

Follow these steps to properly wire your Leviton 2761 locking plug. Refer to the accompanying video for visual guidance.

Video: This video demonstrates the wiring process for Leviton Black and White Plugs and Connectors, including the steps for disassembling, preparing wires, making connections, and reassembling the device.

  1. Assicurarsi che l'alimentazione sia disattivata: Before beginning, verify that the power to the cable is completely off at the circuit breaker to prevent electrical shock.
  2. Identify Plug Configuration: The faceplate of the plug is stamped with the NEMA configuration, ampepoca e voltage. Confirm these match your requirements.
  3. Smontare la spina:
    • Using a Phillips head screwdriver, loosen the quick screws on the faceplate.
    • Carefully remove the faceplate from the body housing.
    • Loosen the two strain relief screws on the strain relief component.
  4. Preparare il cavo:
    • Feed the cable through the loosened strain relief and then through the body housing.
    • Strip the cord jacket according to the diagram on the instruction sheet (typically about 1.5 inches). Remove the stripped cord jacket to expose the individual wires.
  5. Prepare Individual Wires:
    • Cut the green (ground) wire to approximately 1 inch in length.
    • Strip approximately 5/8 inch of insulation from all remaining wires using wire strippers.
  6. Collegare il filo di terra:
    • Insert the green (ground) wire into the wire well of the green (ground) terminal screw, located in the center of the device.
    • Tighten the terminal screw securely with a Phillips head screwdriver.
  7. Collegare il filo neutro:
    • Insert the white (neutral) wire into the wire well of the silver terminal screw.
    • Tighten the terminal screw securely.
  8. Connect Remaining Wires:
    • Insert the remaining three wires into the wire wells of the brass terminals.
    • Tighten each brass terminal screw securely.
  9. Rimontare la spina:
    • Slide the faceplate back into the body housing, ensuring the channel guide on the body housing aligns perfectly with the faceplate.
    • Tighten the quick screws on the faceplate with a Phillips head screwdriver.
  10. Protezione antistrappo sicura:
    • Tighten both screws on the strain relief to secure the cable.
    • Nota: If your wire is larger than the groove on the strain relief, a section of the strain relief can be removed to accommodate larger wire sizes.

Operazione

Once properly wired and assembled, the Leviton 2761 locking plug is ready for use. Insert the plug into a compatible NEMA L19-30R receptacle and twist to lock it into place, ensuring a secure electrical connection. To disconnect, twist in the opposite direction and pull.

Manutenzione

Regularly inspect the plug for any signs of wear, damage, or loose connections. Ensure the cable jacket and strain relief are intact to prevent wire exposure. Clean the plug exterior with a dry cloth as needed. Do not use abrasive cleaners or solvents. If any damage is observed, discontinue use and replace the plug.

Risoluzione dei problemi

Garanzia e supporto

This Leviton product is covered by a manufacturer's warranty. For specific warranty details, claims, or technical support, please contact Leviton customer service directly or visit their official websito. Conservare la ricevuta d'acquisto per motivi di garanzia.

Documenti correlati - 2761

Preview Leviton EV40P EV Serie 40 AMP Manuale di installazione del caricabatterie plug-in
Manuale di installazione per Leviton EV40P EV Series 40 AMP Caricabatterie plug-in per veicoli elettrici. Include avvertenze di sicurezza, specifiche, fasi di installazione, procedure operative, utilizzo della scheda RFID, messaggi di errore, informazioni sulla manutenzione e sulla garanzia.
Preview Guida all'app My Leviton: controlla i tuoi dispositivi Smart Home
Esplora la guida all'app My Leviton per registrare, integrare e personalizzare facilmente i tuoi dispositivi Decora Smart Wi-Fi e Leviton Load Center con Smart Breakers per un controllo della casa intelligente senza interruzioni.
Preview Leviton Decora Smart Wi-Fi Mini Plug-In Dimmer (2a generazione) - Guida introduttiva
Guida completa per il Leviton Decora Smart Wi-Fi Mini Plug-In Dimmer (2a generazione). Scopri come installarlo, configurarlo con Alexa, Google Assistant e Apple HomeKit, risolvere i problemi e avere informazioni sulla sicurezza.
Preview Leviton Decora Smart Wi-Fi Outdoor Plug-In Switch: Guida introduttiva
Scopri come installare e configurare il tuo interruttore plug-in per esterni Leviton Decora Smart Wi-Fi (D2150) per il controllo intelligente di illuminazione ed elettrodomestici da esterno. Include configurazione, associazione e risoluzione dei problemi.
Preview La mia guida all'app Leviton: controllo della casa intelligente per Decora Smart Wi-Fi e centri di carico
Una guida completa all'utilizzo dell'app My Leviton per la gestione dei dispositivi Leviton Decora Smart Wi-Fi e dei centri di carico Leviton con interruttori intelligenti. ...
Preview Leviton Scene Capable Plug-In Lamp Istruzioni per l'installazione del modulo dimmer RZP03-1LW
Istruzioni di installazione per Leviton Scene Capable Plug-In Lamp Modulo dimmer (codice articolo RZP03-1LW). Questa guida illustra la configurazione, l'inclusione nella rete Z-Wave, il funzionamento e la risoluzione dei problemi per il controllo intelligente dell'illuminazione.