HT-Instruments COMBI 420

HT-Instruments Logo

Manuale d'uso del tester multifunzione VDE 0100 COMBI 420 di HT-Instruments

Model: COMBI 420

1. Introduzione

This user manual provides comprehensive instructions for the safe and effective operation of the HT-Instruments COMBI 420 Multifunction VDE 0100 Tester. The COMBI 420 is an advanced and versatile instrument designed for quick and easy verification of electrical installations. It performs tests in accordance with VDE (EN61557) parts 2, 3, 4, 6, and 7, and includes single-phase network analysis capabilities. Please read this manual thoroughly before using the device to ensure proper functionality and user safety.

2. Informazioni sulla sicurezza

Avvertimento: Electrical testing can be hazardous. Always follow local safety regulations and procedures. Failure to do so may result in injury or damage to the equipment.

3. Prodotto finitoview

The HT-Instruments COMBI 420 is a robust and user-friendly multifunction tester. It features a large, clear LCD screen with backlight and a graphical help menu for intuitive operation.

HT-Instruments COMBI 420 Multifunction Tester

Figure 3.1: HT-Instruments COMBI 420 Multifunction Tester. The device features a large LCD display, navigation buttons, and input terminals for various measurements.

3.1 Caratteristiche principali

3.2 Contenuto della confezione

The COMBI 420 package includes:

4. Impostazione

4.1 Installazione della batteria

The COMBI 420 requires 6 AA alkaline batteries. These are typically included with the device. To install or replace batteries:

  1. Assicurarsi che il dispositivo sia spento.
  2. Individuare il vano batteria sul retro del dispositivo.
  3. Aprire il coperchio del vano.
  4. Inserire 6 batterie AA, rispettando la polarità corretta (+/-) come indicato all'interno del vano.
  5. Chiudere saldamente il coperchio del vano batterie.

4.2 Collegamento dei puntali e degli accessori

Connect the appropriate test leads and accessories to the input terminals on the COMBI 420 based on the measurement you intend to perform. Always ensure connections are secure.

5. Istruzioni per l'uso

5.1 Accensione/Spegnimento

Premere il tasto ENERGIA button to turn the device on. The device will perform a self-test and display the main menu. To turn off, press and hold the ENERGIA button, or allow the automatic shutdown feature to activate after a period of inactivity.

5.2 Navigazione e visualizzazione

Utilizzare i pulsanti direzionali e ENTRARE button to navigate through the menus and select functions. The large LCD screen displays measurement results, settings, and the graphical help menu. Press ESC/MENU to return to the previous menu or access the main menu. The AIUTO button provides on-screen assistance for current functions.

5.3 Funzioni di misura

The COMBI 420 offers a wide range of measurement capabilities. Always refer to the on-screen help or specific sections of this manual for detailed connection diagrams and procedures for each test.

  1. Low-Ohm Measurement (Continuity):

    Measures resistance with a test current of >200 mA DC, compliant with VDE 0413 part 4 (EN 61557-4). Used to verify the continuity of protective conductors and equipotential bonding.

  2. Prova di isolamento:

    Performs insulation resistance measurements at 50, 100, 250, 500, or 1000 V DC, compliant with VDE 0413 part 2 (EN 61557-2). Essential for checking the integrity of insulation in electrical systems.

  3. FI (RCD) Test and Analysis:

    Comprehensive testing of Residual Current Devices (RCDs) according to VDE 0413 part 6 (EN 61557-6). Includes trip time, trip current, and contact voltage misurazioni.

  4. Loop and Network Impedance Measurement:

    Measures loop impedance and network impedance, compliant with VDE 0413 part 3 (EN 61557-3). This is crucial for determining prospective fault current and ensuring proper circuit breaker operation.

  5. Short-Circuit Current Ik Display:

    Displays the calculated prospective short-circuit current (Ik) based on impedance measurements, as per VDE 0413 part 3 (EN 61557-3).

  6. Loop Resistance without RCD Tripping:

    Allows loop resistance measurement in circuits protected by RCDs without causing the RCD to trip, using a low test current.

  7. Rotating Field Direction Measurement:

    Determines the phase sequence (rotating field direction) in three-phase systems, compliant with VDE 0413 part 7 (EN 61557-7). This can be performed even with a single test probe.

  8. Power Measurement and Harmonic Analysis:

    Measures active, reactive, and apparent power, as well as power factor. Performs harmonic analysis of voltage and current up to the 49th harmonic and calculates Total Harmonic Distortion (THD) in percentage.

  9. External Probe Measurements:

    When connected, the device can display readings from external humidity, temperature, light (lux), and sound level probes.

5.4 Archiviazione e trasferimento dei dati

The COMBI 420 has an internal memory capable of storing up to 600 measurement values. Use the SALVA button to store current measurement results. Data can be transferred to a PC using the integrated optical USB interface and the provided Topview software.

6. Manutenzione

6.1 Pulizia

Pulire regolarmente il dispositivo con un panno morbido e asciutto. Non utilizzare detergenti abrasivi o solventi. Assicurarsi che non penetri umidità nel dispositivo.

6.2 Sostituzione della batteria

Replace batteries when the low battery indicator appears on the display. Refer to Section 4.1 for battery installation instructions. Always use new, high-quality AA alkaline batteries.

6.3 Calibrazione

For continued accuracy and compliance, periodic calibration by an authorized service center is recommended. The device is supplied with an ISO 9000 calibration protocol, indicating its initial calibration status.

7. Risoluzione Dei Problemi

If you encounter issues with your COMBI 420, try the following basic troubleshooting steps:

For more complex issues, utilize the device's built-in graphical help menu or contact HT-Instruments technical support.

8. Specifiche

CaratteristicaSpecificazione
Numero di modelloCOMBI 420
ProduttoreHT-Instruments
Dimensioni del prodotto (L x P x A)24 x 17 x 8 cm (circa 9.45 x 6.69 x 3.15 pollici)
Peso3 kg (circa 6.6 libbre)
Fonte di alimentazioneBattery-Powered (6 AA batteries required, included)
Conformità alla sicurezzaIEC-1010-1, CAT III 415 V
Standard di misurazioneVDE (EN61557) parts 2, 3, 4, 6, 7
Memoria interna600 valori di misurazione
InterfacciaUSB ottica
Componenti inclusiSuperioreview software, USB cable, storage bag, measurement cable with earthed plug, 3 safety test leads, 2 test probes, 3 crocodile clips, batteries, user manual, ISO 9000 calibration protocol

9. Garanzia e supporto

HT-Instruments products are manufactured to high quality standards. For specific warranty information, please refer to the documentation included with your purchase or visit the official HT-Instruments website. For technical support, service, or inquiries regarding calibration, please contact your local HT-Instruments distributor or customer service department.

Documenti correlati - COMBI 420

Preview Tester multifunzione COMBI521: sicurezza elettrica, qualità dell'alimentazione e test EVSE
Specifiche tecniche complete per il tester multifunzione COMBI521 di HT Instruments, che ne descrivono le capacità per test di sicurezza degli impianti elettrici, analisi della qualità dell'energia e test di sicurezza EVSE. Include funzioni di misura, dati tecnici dettagliati, specifiche generali e informazioni sulla conformità.
Preview Manuale utente HT Instruments PV-ISOTEST
Manuale utente completo per HT Instruments PV-ISOTEST, che descrive in dettaglio le precauzioni di sicurezza, le funzioni dello strumento, le istruzioni operative, le specifiche tecniche e la risoluzione dei problemi per i test di isolamento fotovoltaico.
Preview Specifiche e caratteristiche del misuratore di isolamento/continuità portatile HT Instruments M70
Detailed specifications, features, and reference standards for the HT Instruments M70 handheld insulation and continuity meter, capable of up to 1000VDC. Includes information on electrical tests, power, and operating conditions, along with services offered by EURO-INDEX.
Preview Scheda tecnica del multimetro di sicurezza professionale multifunzione NEPTUNE di HT Instruments
Scheda tecnica completa per il multimetro di sicurezza professionale NEPTUNE di HT Instruments. Fornisce informazioni dettagliate su specifiche elettriche, caratteristiche, alimentazione, condizioni ambientali e conformità.
Preview HT Instruments HT7 Digital Voltage Manuale dell'utente del tester
Manuale utente completo per il misuratore di volume digitale HT Instruments HT7tage tester, che copre istruzioni di sicurezza, procedure operative, specifiche tecniche e manutenzione per un utilizzo sicuro ed efficace.
Preview HT Instruments MACROTESTG3 Tester di sicurezza per installazioni professionali - Specifiche e caratteristiche
Specifiche tecniche dettagliate, parametri elettrici, capacità di test RCD, impedenza di loop, resistenza di isolamento, voltagMisurazioni di corrente, fattore di potenza e armoniche del tester di sicurezza per installazioni professionali MACROTESTG3 di HT Instruments.