1. Introduzione
This manual provides comprehensive instructions for the installation, operation, and maintenance of your Dinuy Terminal Micro 5 Digital Time Switch. Please read this manual carefully before using the device to ensure safe and efficient operation. This device is designed to control electrical circuits based on programmed time schedules.
2. Informazioni importanti sulla sicurezza
- Rischio elettrico: Installation and maintenance should only be performed by a qualified electrician in accordance with all local and national electrical codes.
- Disconnect power at the main circuit breaker before installing or servicing the device.
- Non esporre il dispositivo a umidità, temperature estreme o ambienti corrosivi.
- Assicurarsi che tutti i collegamenti siano sicuri e adeguatamente isolati per evitare cortocircuiti.
- Non superare la capacità di carico massima specificata per il dispositivo.
3. Prodotto finitoview
The Dinuy Terminal Micro 5 is a compact digital time switch designed for DIN rail mounting. It features a clear LCD display for time and program status, along with intuitive buttons for easy programming.

Figure 1: Dinuy Terminal Micro 5 Digital Time Switch
This image displays the Dinuy Terminal Micro 5 digital time switch. The device is white, designed for DIN rail mounting. The top section shows terminals labeled '1' and '2' for power input. Below this, there are terminals '1', '2', '3' for the switched output, with a rating of 'μ16(6)A 250V~'. The central part features a digital LCD screen displaying 'DINUY', '18.06.18', 'LUNES' (Monday), 'On', and '9:28.00'. Below the screen are four blue buttons: 'M' (Mode), 'OK', '-' (Minus/Left arrow), and '+' (Plus/Right arrow). The bottom section shows terminals 'N' (Neutral) and 'L' (Live) for the main power supply, with '230V/50-60Hz' indicated.
3.1. componenti
- Schermo LCD: Shows current time, day, program status, and programming menus.
- Pulsante 'M' (Modalità): Used to navigate through different modes (e.g., time setting, program setting).
- Pulsante 'OK': Conferma le selezioni e le impostazioni.
- '-' Button (Minus/Left Arrow): Decreases values or moves left in menus.
- '+' Button (Plus/Right Arrow): Increases values or moves right in menus.
- Terminali L e N: Main power supply input (230V/50-60Hz).
- Terminal 1, 2, 3: Switched output contacts (μ16(6)A 250V~).
4. Installazione e configurazione
4.1. Montaggio
The Dinuy Terminal Micro 5 is designed for DIN rail mounting. Snap the device onto a standard 35mm DIN rail in your electrical panel.
4.2. Schema elettrico
ATTENZIONE: prima di procedere al cablaggio, assicurarsi che l'alimentazione sia scollegata.
- Connect the main Live (L) wire to the 'L' terminal at the bottom of the device.
- Connect the main Neutral (N) wire to the 'N' terminal at the bottom of the device.
- For the switched output, connect the load's Live wire to terminal '1' or '3' (depending on desired contact type, typically '1' for normally open).
- Connect the incoming Live wire for the load to terminal '2'.
- Refer to the markings on the device for precise terminal identification: Input power (L, N) and Switched output (1, 2, 3).
4.3. Accensione iniziale
After wiring, restore power. The display should illuminate. If the display is blank, check power connections. The device may require initial time and date setting.
5. Istruzioni per l'uso
5.1. Impostazione dell'ora e del giorno correnti
- Press the 'M' button repeatedly until the time setting mode is displayed (e.g., flashing hours).
- Use the '+' and '-' buttons to adjust the hour. Press 'OK' to confirm.
- Repeat for minutes, then for the current day of the week.
- Press 'OK' to save and exit the time setting mode.
5.2. Programmazione degli orari di accensione/spegnimento
The device allows setting multiple ON/OFF programs for different days or groups of days.
- Press the 'M' button until 'PROG' or a similar indicator appears.
- Use '+' or '-' to select a program number (e.g., '1 ON'). Press 'OK'.
- Set the desired ON time (hour and minute) using '+' and '-' and confirming with 'OK'.
- Select the days for this program (e.g., Mon-Fri, daily, specific days) using '+' and '-' and confirming with 'OK'.
- Repeat for the corresponding OFF time ('1 OFF').
- Continuare per altri programmi, se necessario.
- Press 'M' to exit programming mode and return to normal operation.
5.3. Azionamento manuale
To temporarily override the programmed schedule, press the 'M' button briefly during normal operation. This will cycle through 'ON', 'OFF', and 'AUTO' modes. Select 'AUTO' to resume programmed operation.
6. Manutenzione
The Dinuy Terminal Micro 5 requires minimal maintenance. Ensure the device is kept clean and free from dust. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.
7. Risoluzione Dei Problemi
- Il dispositivo non si accende: Check main power supply and wiring connections (L and N terminals). Ensure the circuit breaker is on.
- Il carico non commuta: Verify that the program is correctly set and the device is in 'AUTO' mode. Check the load's wiring and functionality. Ensure the load does not exceed the device's maximum switching capacity.
- Visualizzazione dell'ora errata: Reset the current time and day as per section 5.1.
- Programmi non in esecuzione: Ensure the device is in 'AUTO' mode. Recheck program settings for correct ON/OFF times and selected days.
8. Specifiche tecniche
| Caratteristica | Specificazione |
|---|---|
| Produttore | Dinuy |
| ID prodotto del produttore | IH TER MC5 |
| Numero di modello | terminal micro 5 |
| Ingresso volumetage | 230 V CA, 50-60 Hz |
| Capacità di commutazione | μ16(6)A 250V~ |
| Tipo di montaggio | Guida DIN |
| Dimensioni del pacco | Dimensioni: 11.2 x 6.8 x 5 cm |
| Peso del prodotto | 100 grammi |
9. Informazioni sulla garanzia
This product is covered by the manufacturer's standard warranty. Please refer to the warranty card included with your purchase or contact Dinuy customer support for detailed warranty terms and conditions. Keep your proof of purchase for warranty claims.
10. Assistenza clienti
For technical assistance, troubleshooting not covered in this manual, or warranty inquiries, please contact your local Dinuy distributor or visit the official Dinuy websito per le informazioni di contatto.