Mastercool 96236

Manuale di istruzioni del set di manometri in alluminio a 4 vie Mastercool 96236

For R410A, R22, R407C Refrigerant Systems

Introduzione

This manual provides instructions for the proper setup, operation, and maintenance of your Mastercool 96236 4-Way Aluminum Manifold Gauge Set. This professional-grade tool is designed for use with R410A, R22, and R407C refrigerants in automotive and HVAC/R air conditioning systems. Please read this manual thoroughly before use to ensure safe and efficient operation.

Prodotto finitoview e componenti

The Mastercool 96236 manifold set includes a robust aluminum manifold block, two 2 1/2" gauges, and a set of hoses designed for various refrigerant applications.

  • Manifold Block: Features a 4-way design with a full 3/8" bore for increased flow. Equipped with ball valves that rotate 90° for quick opening and closing.
  • Indicatori: Two 2 1/2" gauges (PSI, °F) for precise pressure and temperature readings. Color-coordinated for multi-refrigerant recognition (R410A, R22, R407C).
  • Tubi flessibili: Includes three 36" 1/4" SAE blue, red, and yellow nylon barrier ball valve hoses with manual shut-off valves, and one 36" 3/8" SAE black vacuum hose.
Mastercool 96236 4-Way Aluminum Manifold Gauge Set with Hoses

Figura 1: Mastercool 96236 4-Way Aluminum Manifold Gauge Set. This image displays the complete manifold set, including the central aluminum block with two large gauges (blue for low pressure, red for high pressure), and four color-coded hoses (red, blue, yellow, and black) coiled around the unit. The hoses are equipped with brass fittings and manual shut-off valves. A metal hook for hanging the manifold is visible at the top.

Istruzioni di installazione

  1. Ispezionare i componenti: Before each use, visually inspect all components for damage, wear, or leaks. Ensure all hose connections are clean and free of debris.
  2. Collegare i tubi:
    • Collegare il tubo blu to the "LOW" port on the manifold and to the low-side service port of the AC system.
    • Collegare il tubo rosso to the "HIGH" port on the manifold and to the high-side service port of the AC system.
    • Collegare il tubo giallo to the "REF" (refrigerant) port on the manifold. This hose will connect to the refrigerant tank or charging station.
    • Collegare il black vacuum hose to the "VAC" (vacuum) port on the manifold. This hose will connect to a vacuum pump for evacuation.
  3. Connessioni sicure: Hand-tighten all connections, then use a wrench to ensure a snug, leak-free seal. Do not overtighten.

Istruzioni per l'uso

A. System Evacuation

  1. Assicurarsi che tutte le valvole del collettore siano chiuse.
  2. Connect the black vacuum hose to a vacuum pump.
  3. Open the "LOW" and "HIGH" valves on the manifold.
  4. Start the vacuum pump. Monitor the gauges; they should drop into a vacuum.
  5. Allow the pump to run until the desired vacuum level is achieved, typically for 15-30 minutes after reaching the target vacuum, depending on system size.
  6. Close the "LOW" and "HIGH" valves on the manifold, then turn off the vacuum pump.
  7. Osservare i manometri per almeno 10-15 minuti per accertarsi che il vuoto sia mantenuto, indicando che non ci sono perdite nel sistema.

B. Refrigerant Charging

  1. Ensure the system has been properly evacuated and holds vacuum.
  2. Connect the yellow hose to the refrigerant tank.
  3. Slightly open the refrigerant tank valve to purge air from the yellow hose by briefly loosening the connection at the manifold's "REF" port until refrigerant escapes, then retighten.
  4. With the engine off (for automotive AC) or system off (for HVAC/R), open the "LOW" valve on the manifold to allow refrigerant to enter the system. Monitor the low-side gauge.
  5. For liquid charging, invert the refrigerant tank and open the "HIGH" valve briefly, then close it. This method is typically used for initial charge or larger systems. Exercise caution with liquid charging.
  6. Once the desired charge is reached, close the "LOW" and "HIGH" valves on the manifold, then close the refrigerant tank valve.
  7. Disconnect the hoses from the service ports.

C. Pressure Testing

  1. Connect the blue and red hoses to the low and high-side service ports, respectively.
  2. Assicurarsi che tutte le valvole del collettore siano chiuse.
  3. Start the AC system and allow it to stabilize.
  4. Open the "LOW" and "HIGH" valves on the manifold.
  5. Read the pressure values on both gauges. Compare these readings to the manufacturer's specifications for the specific refrigerant and ambient temperature.
  6. Close the "LOW" and "HIGH" valves before disconnecting the hoses.

Manutenzione

  • Pulizia: After each use, wipe down the manifold and hoses with a clean, dry cloth. Avoid using harsh chemicals that could damage the gauges or hose material.
  • Magazzinaggio: Store the manifold set in its original blow-molded case in a clean, dry environment to protect it from dust and physical damage.
  • O-Rings and Gaskets: Periodically inspect O-rings and gaskets in the hose fittings for wear or damage. Replace them as needed to prevent leaks.
  • Calibrazione calibro: While gauges are factory calibrated, significant impacts or prolonged use may affect accuracy. If accuracy is suspected, consult a professional for recalibration.

Risoluzione dei problemi

ProblemaPossibile causaSoluzione
Gli indicatori non leggono correttamenteLoose connections, damaged gauge, incorrect refrigerant selected.Check all connections for tightness. Inspect gauges for physical damage. Ensure correct refrigerant scale is being read.
Il sistema non mantiene il vuotoLeaks in hoses, manifold, or AC system.Inspect all hose connections and O-rings. Check AC system components for leaks using a leak detector.
Il refrigerante non scorreManifold valves closed, hose shut-off valves closed, clogged hose, empty refrigerant tank.Ensure all necessary valves are open. Check refrigerant tank level. Inspect hoses for kinks or blockages.

Specifiche

  • Modello: Mastercool 96236
  • Manifold Type: 4-Way Aluminum
  • Dimensione del calibro: 2 1/2 inches (PSI, °F)
  • Compatibilità del refrigerante: R410A, R22, R407C
  • Configurazione del tubo: Three 36" 1/4" SAE nylon barrier ball valve hoses (blue, red, yellow) with manual shut-off valves; One 36" 3/8" SAE black vacuum hose.
  • Manifold Bore: Full 3/8"
  • Tipo di valvola: 90° Ball Valve with Teflon Washers
  • Materiale: Aluminum (manifold block)
  • Peso dell'articolo: 3 libbre
  • Codice UPC: 700376601596

Garanzia e supporto

Specific warranty details for the Mastercool 96236 are typically provided with the product packaging or can be obtained by contacting Mastercool directly. For technical support or service inquiries, please refer to the contact information provided by Mastercool or your authorized distributor.

Documenti correlati - 96236

Preview Istruzioni per l'uso del collettore intelligente Mastercool Spartan
Comprehensive operating instructions and specifications for the Mastercool Spartan Smart Manifold, a digital HVAC manifold gauge system for precise pressure, temperature, and vacuum measurements, data logging, and refrigerant management.
Preview Catalogo di strumenti e attrezzature per l'aria condizionata automobilistica Mastercool
Esplora l'ampio catalogo Mastercool, che include strumenti professionali per la manutenzione dell'aria condizionata per auto, pompe per vuoto, macchine di recupero, apparecchiature per la rilevazione delle perdite e molto altro. Migliora le tue capacità di riparazione auto con le soluzioni innovative di Mastercool.
Preview Collettore in alluminio compatto a 2 vie Mastercool: istruzioni per l'uso e specifiche
Guida completa per il collettore in alluminio a 2 vie compatto Mastercool, con specifiche, istruzioni per l'uso, avvertenze di sicurezza ed elenco dei componenti. Scopri come utilizzare, manutenere e risolvere i problemi del tuo gruppo manometrico digitale.
Preview Guasto dei componenti del sistema di recupero del refrigerante Twin Turbo Mastercool 69365
Elenco completo dei componenti per il sistema di recupero del refrigerante Mastercool 69365 Twin Turbo, con dettagli sui componenti, descrizioni e numeri di parte per il modello di serbatoio DOT da 50 libbre.
Preview Istruzioni per l'uso del collettore intelligente Mastercool Spartan
Istruzioni operative complete per il Mastercool Spartan Smart Manifold, che coprono la configurazione, l'uso, funzionalità come il test di tenuta e la registrazione dei dati, nonché la manutenzione.
Preview Mastercool Infrared Refrigerant Leak Detector - Operating Instructions
This document provides operating instructions, specifications, safety warnings, and maintenance details for the Mastercool Infrared Refrigerant Leak Detector (Model 55600-A). Learn how to use the device, understand its features, and perform basic maintenance.