Introduzione
This manual provides essential information for the installation, operation, and maintenance of the ESBE VTC422 DN25 Charging Valve. The VTC400 series is specifically designed for integration with buffer tanks in heating systems to ensure optimal performance and longevity.
Per garantire un utilizzo sicuro e corretto, leggere attentamente il presente manuale prima dell'installazione e dell'uso.
Prodotto finitoview
The ESBE VTC422 DN25 is a thermostatic charging valve designed to protect boilers from low return water temperatures. It ensures that the boiler reaches a high operating temperature quickly, which helps to prevent tarring and extends the boiler's lifespan. This model features a G 1" connector and operates within a temperature range of 50-70 °C.

Figura 1: ESBE VTC422 DN25 Charging Valve. This image shows the brass body of the valve with three threaded connections and a black plastic housing at the bottom containing the thermostatic element. The ESBE logo is visible on the side.
Istruzioni di sicurezza
- Always ensure the system is depressurized and cooled before attempting any installation or maintenance.
- Installation should be performed by a qualified professional in accordance with local regulations and standards.
- Indossare adeguati dispositivi di protezione individuale (DPI) durante l'installazione e la manutenzione.
- Do not modify the valve or its components. Use only genuine ESBE spare parts.
- Assicurare la corretta sigillatura di tutti i collegamenti per evitare perdite.
Configurazione e installazione
Controlli prima dell'installazione
- Verify that the valve model (VTC422 DN25) and temperature range (50-70 °C) are suitable for your heating system and boiler.
- Prima dell'installazione, ispezionare la valvola per verificare la presenza di eventuali danni visibili.
- Ensure all necessary tools and fittings (G 1" connectors) are available.
Fasi di installazione
- Position the valve correctly in the heating circuit, typically on the return line to the boiler, before the buffer tank connection. Refer to the system's hydraulic diagram for precise placement.
- Connect the valve to the piping using appropriate G 1" fittings. Ensure connections are tight but do not overtighten.
- The valve has three ports: boiler return, buffer tank return, and boiler supply. Ensure correct flow direction as indicated on the valve body or in the system diagram.
- After installation, slowly fill the system and check for leaks at all connections.
- Bleed air from the system as per boiler manufacturer instructions.
Principi operativi
The ESBE VTC422 DN25 is a thermostatic mixing valve that automatically regulates the temperature of the water returning to the boiler. When the boiler starts, the valve ensures that cold return water from the buffer tank is mixed with hot water from the boiler's flow, quickly raising the boiler's return temperature to the set point (50-70 °C). This prevents condensation and corrosion within the boiler.
Once the boiler reaches its operating temperature and the buffer tank is being charged, the valve gradually opens to allow more hot water from the boiler to flow into the buffer tank, while maintaining the minimum return temperature to the boiler.
Manutenzione
Controlli regolari
- Periodically inspect the valve and connections for any signs of leaks or corrosion.
- Assicurarsi che la pressione del sistema rientri nell'intervallo consigliato.
Pulizia
The valve is generally maintenance-free. If blockages or performance issues occur due to sediment, the system should be flushed. For internal cleaning or replacement of thermostatic elements, it is recommended to consult a qualified technician.
Sostituzione dei componenti
If the thermostatic element or other internal components require replacement, use only original ESBE spare parts. This procedure should be carried out by a trained professional.
Risoluzione dei problemi
| Problema | Possibile causa | Soluzione |
|---|---|---|
| Temperatura ritorno caldaia troppo bassa. | Valve not opening correctly, sediment buildup, incorrect installation. | Check system pressure, flush system, verify installation direction, consult technician. |
| Poor heat transfer to buffer tank. | Valve not opening fully, air in system, incorrect sizing. | Bleed air from system, verify valve operation, ensure correct valve sizing for application. |
| Perdite nei collegamenti. | Loose fittings, damaged seals, incorrect thread sealant. | Tighten connections, replace seals, reapply thread sealant. |
For persistent issues, contact a qualified heating system technician or ESBE customer support.
Specifiche
- Modello: ESBE VTC422 DN25
- Numero parte: 51060600
- Marca: ESBE
- Materiale: Metallo (ottone)
- Tipo di connessione: G 1" (External Thread)
- Diametro nominale (DN): 25
- Intervallo di temperatura: Temperatura: 50-70 °C
- Dimensioni (L x P x A): 5.59 x 8.41 x 12.19 cm (circa 5.6 x 8.4 x 12.2 cm)
- Peso: 771.11 grammi (circa 1.7 libbre)
- Numero di porte: 3
- Finitura esterna: Dipinto
Garanzia e supporto
For warranty information, please refer to the official ESBE website or contact your local ESBE distributor. Keep your proof of purchase for warranty claims.
For technical support, spare parts, or further assistance, please visit the official ESBE website or contact their customer service department. Contact details can typically be found on the ESBE official websito: www.esbe.eu