Value VRR24M-C

Manuale utente dell'unità di recupero del refrigerante Value VRR24M-C

Model: VRR24M-C

Marchio: Valore

Prodotto finitoview

The Value VRR24M-C is a compact and efficient refrigerant recovery unit designed for professional use. It is suitable for recovering various types of refrigerants, including R12, R134a, R407c, R22, R410a, R32, and R1234yf, among others. Its robust design and user-friendly features make it an essential tool for HVAC/R technicians.

Value VRR24M-C Refrigerant Recovery Unit, front-side view

Image: The Value VRR24M-C Refrigerant Recovery Unit, showcasing its compact design, control panel with gauges, and connection ports. The unit features a sturdy handle for portability and a ventilation grille on the side.

Caratteristiche principali:

Informazioni sulla sicurezza

Always read and understand all safety warnings and instructions before operating the VRR24M-C unit. Failure to do so may result in serious injury or equipment damage.

Impostare

  1. Disimballaggio: Carefully remove the VRR24M-C unit from its packaging. Inspect for any shipping damage.
  2. Posizionamento: Place the unit on a stable, level surface in a well-ventilated area, away from direct sunlight or heat sources.
  3. Collegamento elettrico: Connect the power cord to a grounded 230V/50Hz electrical outlet. Ensure the power switch on the unit is in the "OFF" position before connecting.
  4. Collegamenti dei tubi:
    • Connect the appropriate hoses from the system to be recovered to the "IN" port of the recovery unit.
    • Connect a hose from the "OUT" port of the recovery unit to the recovery cylinder.
    • Assicurarsi che tutti i collegamenti siano ben serrati per evitare perdite.
  5. Preparazione del cilindro: Ensure the recovery cylinder is empty and has sufficient capacity for the refrigerant being recovered. Weigh the cylinder before and during recovery to prevent overfilling.

Istruzioni per l'uso

The VRR24M-C unit offers different recovery modes for optimal performance.

Fasi operative generali:

  1. Ensure all hoses are correctly connected and valves are in the appropriate positions (refer to your system's specific recovery procedure).
  2. Portare l'interruttore di alimentazione principale in posizione "ON".
  3. Select the desired recovery mode using the operation knob (e.g., Gas, Liquid, Push/Pull).
  4. Monitor the high and low-pressure gauges during the recovery process.
  5. The unit will automatically shut off if the pressure exceeds 38.5 bar (558 psi).
  6. Once recovery is complete, or the system pressure reaches the desired vacuum level, turn off the unit and close all valves.
  7. Disconnect hoses carefully, being mindful of any residual pressure.

Recovery Efficiency (Approximate):

Refrigerant CategoryModalitàEfficiency (kg/min)
Category III (e.g., R12, R134a, R401c, R406a, R500, R1234yf)Gas2.6
Liquid / Push / Pull7.50
Category IV (e.g., R22, R401a, R401b, R402b, R407c, R407d, R408a, R409a, R502, R509)Gas2.9
Liquid / Push / Pull8.50
Category V (e.g., R402a, R404a, R407a, R407b, R410a, R507, R32)Gas3.9
Liquid / Push / Pull9.50

Note: Recovery efficiency may vary based on ambient temperature, system conditions, and refrigerant type.

Manutenzione

Regular maintenance ensures the longevity and optimal performance of your VRR24M-C unit.

Risoluzione dei problemi

Questa sezione fornisce soluzioni ai problemi operativi più comuni. Per problemi non elencati qui, contattare personale di assistenza qualificato.

ProblemaPossibile causa/soluzione
L'unità non si accende.
  • Controllare che il cavo di alimentazione sia collegato saldamente a una presa di corrente.
  • Verificare che l'interruttore di alimentazione sia in posizione "ON".
  • Controllare l'interruttore automatico o il fusibile della presa di corrente.
Lento tasso di recupero.
  • Ensure hoses are properly connected and not kinked.
  • Check for blockages in hoses or filters.
  • Verify the correct recovery mode (Gas/Liquid) is selected for the refrigerant state.
  • Ambient temperature may be too low (operating temperature 0-40°C).
Unit shuts down automatically.
  • High-pressure shutdown: The pressure may have exceeded 38.5 bar (558 psi). Check for overfilled recovery cylinder or blockages.
  • Overheating: Ensure adequate ventilation around the unit. Allow the unit to cool down.
Refrigerant leaks detected.
  • Tighten all hose connections and fittings.
  • Inspect hoses for damage and replace if necessary.
  • Check O-rings and seals on connections.

Specifiche

ParametroValore
Modello del prodottoModello VRR24M-C
Refrigeranti compatibiliCategory III: R12, R134a, R401c, R406a, R500, R1234yf
Category IV: R22, R401a, R401b, R402b, R407c, R407d, R408a, R409a, R502, R509
Category V: R402a, R404a, R407a, R407b, R410a, R507, R32
Alimentazione elettrica230V / 50Hz
Potenza del motore1 CV
Velocità del motore3000 giri al minuto
Corrente massima5 A
Tipo di compressorePiston compressor, air-cooled, oil-free, maintenance-free
Automatic Shutdown Pressure38.5 bar / 3850 kPa (558 psi)
Temperatura di esercizio0 - 40 °C
Dimensioni (L x P x A)Dimensioni: 370 x 250 x 300 mm
Peso11.5 kg
Dispositivi compatibiliRefrigerator, Air Conditioner, Cooling Unit

Garanzia e supporto

I dettagli specifici della garanzia non sono forniti nelle informazioni sul prodotto. Per i termini e le condizioni della garanzia, fare riferimento alla documentazione di acquisto o contattare il rivenditore/produttore.

For technical support or service inquiries, please contact Value customer service or your authorized dealer.

Documenti correlati - Modello VRR24M-C

Preview Manuale utente dell'unità di recupero VALUE VRR24M-C
Manuale utente per l'unità di recupero refrigerante VALUE VRR24M-C, che descrive in dettaglio sicurezza generale, funzionamento, specifiche, parti, cablaggio e risoluzione dei problemi.
Preview VALUE VRR12L-R32 / VRR24L-R32 Recovery Unit Manual
This manual provides operating instructions, safety guidelines, and troubleshooting tips for the VALUE VRR12L-R32 and VRR24L-R32 Recovery Units. It covers essential information for safe and efficient refrigerant recovery.
Preview Manuale utente e informazioni tecniche della pompa per vuoto azionata da inverter VALUE VRP-15DN
Guida completa per la pompa per vuoto a inverter VALUE VRP-15DN, che comprende specifiche tecniche, applicazioni, precauzioni di sicurezza, istruzioni operative, procedure di manutenzione, guida alla risoluzione dei problemi ed elenco dei componenti. Progettata per sistemi HVACR e refrigeranti come ammoniaca, R-32 e R-1234yf.
Preview Manuale operativo dello strumento di svasatura per batterie agli ioni di litio VALUE VET-19Li
Manuale operativo per lo strumento di svasatura per batterie agli ioni di litio VALUE VET-19Li, contenente linee guida di sicurezza, specifiche tecniche, istruzioni per l'uso, procedure di ricarica e risoluzione dei problemi.
Preview Manuale utente dell'espansore di tubi di potenza della serie VALUE VTE - Funzionamento e specifiche
Manuale d'uso per l'espansore di tubi di potenza serie VALUE VTE (modelli VTE-29D, VTE-42D). Include istruzioni su carica, cambio dell'olio, lubrificazione, sicurezza, funzionamento, scarico della pressione e specifiche tecniche.
Preview VALUE VRR24M-C Refrigerant Recovery Unit - Product Overview E specifiche
Dettagliato sopraview and specifications for the VALUE VRR24M-C Refrigerant Recovery Unit, featuring a DC brushless motor, oil-free compressor, and suitability for R32 refrigerant. This unit offers fast recovery, better visibility, and a self-purge function.