EASTRON SDM630MCT-MODBUS-MID

Manuale utente del contatore elettrico EASRON SDM630MCT V2

Model: SDM630MCT-MODBUS-MID

1. Introduzione e oltreview

The EASTRON SDM630MCT-Modbus Power Consumption Monitor is a robust device designed for precise monitoring and management of single and three-phase electrical usage. It features an easy-to-read digital backlit LCD display, ensuring clear data visibility in various lighting conditions. This meter facilitates seamless integration with other systems via its Modbus RS485 communication function.

The SDM630MCT-Modbus accurately measures a comprehensive range of electrical parameters, including voltage, frequency (Hz), current (A), power (KW/kVA/kVAr), and both import, export, and total energy (kWH/kVArh). This detailed measurement capability assists users in identifying areas for energy consumption reduction, leading to potential energy and cost savings.

EASTRON SDM630MCT V2 Electricity Meter front view

Figura 1: Fronte view of the EASTRON SDM630MCT V2 Electricity Meter, showing the LCD display and control buttons.

2. Caratteristiche principali

Diagram showing features of EASTRON SDM630MCT Modbus DIN Rail Meter

Figure 2: Key features and capabilities of the SDM630MCT Modbus meter, highlighting its multi-function power analysis.

Dettagliato view of EASTRON SDM630MCT V2 features like Pulse LED, LCD, and sealing hole

Figura 3: primo piano view illustrating the Pulse LED, LCD Backlight Display, functional touch buttons, sealing hole, and 35mm DIN rail mounting.

3. Configurazione e installazione

The EASTRON SDM630MCT V2 is designed for DIN rail mounting within an electrical enclosure. Proper installation requires knowledge of electrical systems and adherence to local electrical codes. It is strongly recommended that installation be performed by a qualified electrician.

3.1 Current Transformer (CT) Connection

This meter requires external Current Transformers (CTs) for operation. CTs are essential for measuring current in high-amperage circuits and provide isolation between the measurement device and the main power lines. The meter supports 1A or 5A CT inputs. Ensure the CTs are correctly sized for your application and connected according to the wiring diagram provided in the full product manual.

CT-powered meters are widely used to monitor power grid operation. Multiple CTs may be installed for different applications, such as protective devices and revenue measurement, to ensure proper isolation and allow for CTs with varying characteristics (accuracy, overload capacity).

3.2 Modbus RS485 Connection

The Modbus RS485 interface allows the meter to communicate with other devices, such as data loggers, PLCs, or building management systems. Connect the RS485 A and B terminals to your Modbus network. Ensure proper polarity and termination resistors are used as per Modbus standards. The meter's Modbus address can typically be configured via the device's menu.

3.3 Installazione fisica

  1. Mount the meter securely on a standard 35mm DIN rail within an appropriate electrical enclosure.
  2. Collegare il volumetage inputs (L1, L2, L3, N) as per your single or three-phase system configuration.
  3. Connect the secondary windings of the Current Transformers to the meter's CT input terminals. Ensure correct phase and direction.
  4. Connect the Modbus RS485 communication lines (A and B) and any pulsed output lines if required.
  5. After installation, the sealing hole can be used to apply a safety seal, preventing unauthorized tampring.

Nota: Questo manuale fornisce una panoramica generaleview. For detailed wiring diagrams, safety precautions, and specific installation steps, please refer to the complete installation guide provided with your product or consult a qualified electrician.

4. Istruzioni per l'uso

The EASTRON SDM630MCT V2 features an intuitive interface for easy operation and data retrieval.

4.1 Display LCD e navigazione

The backlit LCD display provides real-time readings of various electrical parameters. Navigation through the display screens and configuration menus is done using the front panel buttons (typically 'M' for Menu/Mode, 'Up' and 'Down' arrows for navigation, and 'Enter' for selection).

4.2 Viewmisurazioni

Upon power-up, the meter typically displays the total energy (kWh). Use the navigation buttons to cycle through different measurement screens, which may include:

4.3 Configuration (Advanced Users)

The meter allows configuration of various settings, such as the CT ratio, Modbus address, baud rate, and pulse output parameters. Accessing and modifying these settings typically involves entering a password-protected menu. Refer to the detailed product manual for specific instructions on menu navigation and parameter configuration.

Per esempioample, some users have reported that when connecting to specific inverters (e.g., Growatt), the Modbus address may need to be set to '2' for proper communication.

Nota: Incorrect configuration can lead to inaccurate readings or communication issues. Only modify settings if you are familiar with the required parameters.

5. Manutenzione

The EASTRON SDM630MCT V2 is designed for long-term, reliable operation with minimal maintenance. However, periodic checks can help ensure optimal performance:

Avvertimento: Always disconnect power to the meter and associated circuits before performing any inspection or maintenance to prevent electric shock.

6. Risoluzione Dei Problemi

This section provides solutions to common issues you might encounter with your EASTRON SDM630MCT V2 meter. If the problem persists, contact technical support.

ProblemaPossibile causaSoluzione
Meter display is blank or not powering on.No power supply to the meter; incorrect wiring; internal fault.
  • Verificare che il volumetage inputs (L1, L2, L3, N) are correctly wired and receiving power.
  • Controllare gli interruttori automatici o i fusibili.
  • Assicurarsi che tutti i collegamenti siano sicuri.
Readings are inaccurate or zero.Incorrect CT wiring (polarity, ratio); incorrect meter configuration; faulty CT.
  • Verify CT wiring, ensuring correct polarity and connection to the meter's terminals.
  • Confirm the CT ratio configured in the meter matches the physical CTs installed.
  • Ensure CTs are correctly installed around the phase conductors.
Modbus communication failure.Incorrect Modbus address; incorrect baud rate; wiring issues (A/B swapped, no termination); incompatible inverter/device.
  • Check the meter's Modbus address and ensure it is unique on the network. (e.g., for Growatt inverters, try setting address to '2').
  • Verify the baud rate, parity, and stop bits match between the meter and the Modbus master.
  • Ensure RS485 A and B lines are not swapped and proper termination resistors are used.
  • Confirm compatibility with the connected inverter or device (e.g., some users reported issues with SOLAX inverters).
Meter not responding to button presses.Temporary software glitch; physical button damage.
  • Cycle power to the meter (turn off and on).
  • Se il problema persiste, contattare l'assistenza.

Disclaimer: This troubleshooting guide covers common issues. For complex problems or if you are unsure, always consult a qualified professional or EASTRON technical support.

7. Specifiche

Below are the technical specifications for the EASTRON SDM630MCT V2 Electricity Meter.

Detailed specification table for EASTRON SDM630MCT V2

Figure 4: Comprehensive technical specification table for the SDM630MCT V2 meter.

CategoriaParametroValore
Specificazionevolume nominaletage (non)3x230/400V AC
Volume operativotage80% - 120% of Un
Insulation capabilities - AC voltage resistere4KV per 1 minuto
Insulation capabilities - Impulse voltage resistere6KV - 1.2µS
Rated current (Ib)5A CT or 333mV CT input
Intervallo di corrente operativa0.4% Ib - Imax
Resistenza alla sovracorrente20 Imax per 0.01 s
Gamma di frequenza operativa50 o 60 Hz
Power consumption per phase≤ 2W/10VA
Uscita impulsiva 1Configurabile
Uscita impulsiva 23200 Imp/kWh
DisplayLCD
Lettura massima999999.9 kWh/kVArh
Criteri di rendimentoUmidità di esercizio≤ 90%
Umidità di stoccaggio≤ 95%
Temperatura di esercizio-25°C - +55°C
Temperatura di conservazione-40°C - +70°C
Temperatura di riferimento23°C ± 2°C
Standard internazionaleIEC 62053-21 / EN50470-1/3
Classe di precisioneClass 1 / Class B
AmbientaleCategoria di installazioneCAT III
Ambiente meccanicoM1
Ambiente elettromagneticoE2
Grado di inquinamento2
Protezione contro la penetrazione di polvere e acquaIP51 (interno)
Contatore con custodia isolante di classe protettivaII
Compatibilità elettromagneticaScariche elettrostatiche8KV contact / 15KV air gap
Radiated & conducted emissionsLa norma EN 55022
PrecisioneVoltage, corrente1.0 % or 0.5% option available
Frequenza0.2% della media frequenza
Fattore di potenza1% of Unity (0.01)
Active power / Apparent power±1% della portata massima
Potenza reattiva±1% della portata massima
Energia reattiva (kVArh)Classe 2
Energia attiva (kWh)Classe 1
Dimensioni del prodotto10.3 x 11 x 8 cm; 290 grammi
ModbusTipo di autobusRS485 (semi-duplex)
ProtocolloModbus-RTU
Velocità in baud2400/4800/9600/19200/38400bps
Intervallo di indirizzi1-247
Max. Bus loading64 pezzi
Distanza di comunicazione1000 metri
ParitàPARI/DISPARI/NESSUNO
Bit di dati8
Smettila un po '1
Dimensions diagram of EASTRON SDM630MCT V2

Figure 5: Dimensional drawing of the EASTRON SDM630MCT V2, showing height, width, and depth.

8. Garanzia e supporto

EASTRON is committed to providing high-quality electrical measurement instruments. While specific warranty details are not provided in this document, standard manufacturer warranties typically cover defects in materials and workmanship for a defined period from the date of purchase.

For warranty claims, technical assistance, or to obtain the full product documentation (including detailed wiring diagrams and advanced configuration guides), please contact EASTRON customer support or your authorized reseller. Many users have reported positive experiences with EASTRON's responsiveness in providing necessary documentation and support.

You can typically find contact information on the official EASTRON websito o tramite la documentazione di acquisto.

SGS Certificate for EASTRON products, highlighting quality and reliability

Figure 6: EASTRON's commitment to quality and reliability, as evidenced by certifications like the SGS EU Type Examination Certificate.

EASTRON's focus on innovation, quality, and competitive edge in smart meters

Figure 7: EASTRON's dedication to innovation and quality in the development of intelligent meters.

Documenti correlati - SDM630MCT-MODBUS-MID

Preview Manuale utente del contatore di energia per guida DIN Eastron SDM630MCT da 40 mA
Guida completa al contatore di energia Eastron SDM630MCT da 40 mA per guida DIN, che ne illustra caratteristiche, misurazioni, configurazione e specifiche per sistemi elettrici monofase e trifase.
Preview Manuale utente del contatore di energia intelligente Eastron SDM630MCT-MOD-MID
Manuale utente completo per il contatore di energia intelligente Eastron SDM630MCT-MOD-MID DIN Rail, che descrive in dettaglio le sue caratteristiche, specifiche, configurazione e installazione per sistemi elettrici monofase e trifase. Copre la misurazione della tensionetage, current, power, energy, and communication protocols like Modbus RTU.
Preview Manuale utente del contatore di energia multifunzione Eastron SDM630MCT V2 Series
Manuale utente per i contatori di energia multifunzione Eastron serie SDM630MCT V2, che descrive in dettaglio installazione, funzionamento, configurazione e specifiche per sistemi elettrici monofase e trifase.
Preview Manuale utente del contatore di energia intelligente su guida DIN EASTRON SDM630M CT-2T
Manuale utente per il contatore di energia intelligente EASTRON SDM630M CT-2T per guida DIN, che descrive in dettaglio le sue caratteristiche, specifiche, procedure di installazione e configurazione per sistemi elettrici monofase e trifase. Include misurazioni, comunicazione e impostazioni operative.
Preview Manuale utente del contatore intelligente su guida DIN Eastron SDM630-EV
Manuale utente per il contatore intelligente Eastron SDM630-EV per guida DIN, che descrive in dettaglio caratteristiche, specifiche, installazione e funzionamento per sistemi elettrici monofase e trifase. Include schemi elettrici, dimensioni e specifiche tecniche.
Preview Manuale utente del contatore di energia multifunzione Eastron SDM630MCT V2 Series
Manuale utente completo per i contatori di energia multifunzione Eastron serie SDM630MCT V2, che copre l'installazione, la configurazione, le specifiche e il funzionamento per sistemi elettrici monofase e trifase.