Elitech LD-100+

Manuale utente del rilevatore di perdite di refrigerante Elitech LD-100+

Model: LD-100+

Marca: Elitech

Introduzione

This manual provides detailed instructions for the safe and effective use of the Elitech LD-100+ Refrigerant Leak Detector. The LD-100+ is an advanced halogen gas leak detector designed for identifying leaks in various refrigeration systems. It features a high-precision heated diode sensor and supports a wide range of refrigerants.

Prodotto finitoview

Caratteristiche principali

  • High-precision heated diode sensor for extended life.
  • Detects R11, R22, R404a, R410a, R600a, R1234yf, and all halogenated refrigerants including CFCs, HFCs, HCFCs, HCs, HFOs, and blends.
  • Two detection modes: Automatic and Manual, suitable for various environments.
  • Fast response: Warms up in 30 seconds, responds in 3 seconds.
  • Three adjustable sensitivity levels with a maximum sensitivity of 0.11 oz/yr.
  • New pump-suction structure for increased sensitivity and anti-water absorption.
  • Meets CE and EN14624 safety standards.

Componenti del prodotto

The image below illustrates the main components of the Elitech LD-100+ Refrigerant Leak Detector.

Elitech LD-100+ Refrigerant Leak Detector with labeled components

Immagine: Labeled diagram of the LD-100+ showing the flexible probe, sensor, battery icon, buzzer icon, alarm icon, auto reset icon, sensitivity icon, auto reset button, On/Off button, mute button, sensitivity button, and battery base.

Tipi di refrigerante supportati

The LD-100+ is capable of detecting a wide range of refrigerants, including:

List of refrigerant types detectable by Elitech LD-100+

Immagine: Visual list of detectable refrigerants including HFCs (R134a, R410a, R407C, R417A, R404A, R507, R23, R508A, R508B, R152A, R32), HCFCs (R22, R123, R124, R141b, R142b, R402A, R402B, R408A, R409A), CFCs (R11, R12, R13, R502, R503), PFCs (PFC-14, PFC-116, PFC-218), HFO (R-1234YF), and HCs (R50, R170, R290, R600, R600A, R1150, R1270).

Impostare

Disimballaggio e ispezione iniziale

Carefully remove the leak detector and all accessories from the packaging. Inspect the device for any signs of damage. The packing list typically includes:

  • 1 x Leak Detector with Heated Diode Gas Sensor
  • 3 batterie AA
  • 1 x Packing Case
  • 1 x Manuale utente
Elitech LD-100+ packing list contents

Immagine: The Elitech LD-100+ leak detector, its packaging, and included accessories such as batteries and user manual.

Installazione della batteria

The LD-100+ requires 3 AA batteries (included). Open the battery compartment located at the base of the device and insert the batteries, ensuring correct polarity. Close the compartment securely.

Elitech LD-100+ dimensions and battery information

Immagine: Diagram showing the dimensions of the LD-100+ (10.4 inches length, 2.3 x 2.1 inches body, 16.5 inches probe length) and battery specifications (3 x AA Battery, ~7 hours battery life).

Istruzioni per l'uso

Prima di utilizzare il dispositivo, familiarizzare con il pannello di controllo.

Elitech LD-100+ control panel with buttons and display

Immagine: Close-up of the LD-100+ control panel showing the digital display, battery indicator, alarm indicator, and buttons for OFF/ON, RESET, SENS (Sensitivity), and MUTE.

Accensione/spegnimento

Premere il tasto SPENTO/ACCESO button to power the device on or off. The device will undergo a brief warm-up period (approximately 30 seconds) before it is ready for use.

Regolazione della sensibilità

The LD-100+ offers three adjustable sensitivity levels to adapt to different leak detection scenarios. Press the SENS button to cycle through the sensitivity levels: High (Red), Medium (Orange), and Low (Green). Higher sensitivity is suitable for detecting very small leaks, while lower sensitivity helps pinpoint larger leaks without false alarms from ambient refrigerant.

Detection Modes (Automatic & Manual Reset)

The device supports both automatic and manual reset modes:

  • Ripristino automatico: Indicated by an 'A' icon on the display. In this mode, the detector automatically sets the current ambient refrigerant concentration as the reference point. This is useful for general scanning.
  • Ripristino manuale: To enter manual reset mode, long-press the RESET button. The device will take the current ambient concentration as the reference point. This mode is particularly useful for finding the exact leak point in an environment where there are already significant refrigerant concentrations.

Funzione silenziosa

Premere il tasto MUTE button to toggle the audible alarm on or off. The visual alarm will remain active regardless of the mute setting.

Procedura di rilevamento delle perdite

  1. Power on the device and allow it to warm up.
  2. Select the appropriate sensitivity level using the SENS pulsante.
  3. Move the probe slowly (approximately 1 inch per second) around the suspected leak area.
  4. When a leak is detected, the device will alarm (audibly and visually), and the display will show an increasing concentration reading.
  5. To pinpoint the exact leak location, use the manual reset mode to re-zero the device in the vicinity of the leak, then move the probe closer to isolate the source.
Elitech LD-100+ features including sensitivity, alarm, anti-water probe, and reset modes

Immagine: Un oltreview of the LD-100+ features, highlighting 3 sensitivity levels, 1 year sensor life, audible & visual alarm, anti-water absorption probe, 2 reset modes (Auto & Manual), and detectable HFCs/HCs.

Elitech LD-100+ with IP65 waterproof rating and new suction structure design

Immagine: Illustrates the IP65 waterproof level and the new suction structure design of the LD-100+, which enhances sensitivity and prevents water absorption.

Manutenzione

Sostituzione del sensore

The heated diode sensor has a limited lifespan and may need replacement if the device consistently provides inaccurate readings or fails to detect refrigerants. Refer to the video below for instructions on how to replace the sensor.

Video: This video demonstrates how to replace the heated diode sensor on the Elitech LD-100+ Refrigerant Leak Detector. It shows the process of unscrewing the old sensor and installing a new one.

Pulizia

Wipe the device with a soft, dry cloth. Do not use abrasive cleaners or solvents. Ensure the sensor tip is free from debris for optimal performance.

Magazzinaggio

Store the leak detector in its protective case in a cool, dry place when not in use. Remove batteries if storing for extended periods to prevent leakage.

Risoluzione dei problemi

Device Alarms Continuously or Fails to Detect Refrigerant

If your leak detector is constantly alarming or not detecting refrigerant as expected, consider the following:

  1. High Refrigerant Concentration in Environment: The ambient refrigerant concentration might be too high, leading to false alarms. Try moving to a clean air environment and resetting the device.
  2. Problemi con il sensore: The sensor may be faulty or at the end of its lifespan. Consider replacing the heated diode sensor as shown in the maintenance section.

The following video provides guidance on self-checking your leak detector for these issues:

Video: This video explains common reasons why the leak detector might alarm continuously or not detect refrigerant, and suggests self-check methods including using the reset button and considering sensor replacement.

If problems persist after performing these checks, please contact Elitech customer support with photos and videos of the issue for further assistance.

Specifiche

AttributoValore
MarcaTecnologia d'élite
ModelloLD-100+
Fonte di alimentazioneBattery Powered (3 x AA Lithium Metal batteries included)
Peso dell'articolo12.32 once
Dimensioni del prodotto2.3 x 2.1 x 10.1 pollici
Tipo di allarmeUdibile
Umidità di esercizio80 percento
Valutazione della temperatura superiore52 gradi Celsius
Tipo di sensoreDiodo riscaldato
Sensibilità massima0.11 oz/yr (3g/yr)
Tempo di risposta≤3 secondi
Tempo di preriscaldamentoAnni 30
Tempo di ripristinoAnni 10
Durata della batteria~7 ore
Temperatura di lavoroTemperatura ambiente: da 0°C a 50°C

Garanzia e supporto

Informazioni sulla garanzia

The Elitech LD-100+ Refrigerant Leak Detector comes with a manufacturer's warranty for 365 days from the date of purchase. Please retain your proof of purchase for warranty claims.

Assistenza clienti

For technical assistance, troubleshooting, or any product-related inquiries, Elitech offers 24/7 US Technician Support via email and phone. Please refer to the contact information provided with your product or on the official Elitech websito.

Documenti correlati - LD-100+

Preview Manuale d'uso del rilevatore di corona Elitech WJL-6000S
Manuale utente per il rilevatore di corona Elitech WJL-6000S, che fornisce istruzioni dettagliate sul funzionamento, il rilevamento, la risoluzione dei problemi e la manutenzione per il rilevamento delle perdite di refrigerante in vari sistemi.
Preview Manuale dell'utente del rilevatore di perdite di refrigerante a infrarossi serie Elitech ILD
Manuale utente completo per i rilevatori di perdite di refrigerante a infrarossi della serie Elitech ILD (ILD-100, ILD-200, ILD-300), che illustra specifiche, funzionamento, manutenzione e caratteristiche. Scopri come rilevare efficacemente le perdite di refrigerante con questo dispositivo avanzato.
Preview Manuale utente del rilevatore di perdite alogeno Elitech HLD-200
This user manual provides comprehensive instructions for operating and maintaining the Elitech HLD-200 Halogen Leak Detector. It covers technical specifications, operation procedures, leak detection methods, troubleshooting, and maintenance tips for effective use in refrigeration and HVAC systems.
Preview Manuale utente del rilevatore di perdite di refrigerante a diodo riscaldato Elitech LD-100
Manuale utente per il rilevatore di perdite di refrigerante a diodo riscaldato Elitech LD-100, che ne descrive in dettaglio le caratteristiche, il funzionamento e la manutenzione.
Preview Manuale utente del rilevatore di perdite a diodo riscaldato e a infrarossi Elitech IR-200
Manuale utente completo per Elitech IR-200, un rilevatore di perdite a doppio sensore con tecnologia a infrarossi e diodo riscaldato. Scopri le specifiche, il funzionamento, la manutenzione e le funzionalità per la rilevazione delle perdite di refrigerante.
Preview Manuale utente del rilevatore di perdite a infrarossi Elitech ILD-100/ILD-200/ILD-300
Manuale utente per i rilevatori di perdite di refrigerante a infrarossi della serie Elitech ILD (ILD-100, ILD-200, ILD-300). Fornisce informazioni dettagliate su funzionamento, specifiche, caratteristiche e manutenzione per un rilevamento accurato delle perdite di refrigerante.