Eastron SDM630-MODBUS-MID V3

Manuale utente del contatore elettrico digitale trifase Eastron SDM630Modbus-V3

Model: SDM630-MODBUS-MID V3

1. Introduzione

The Eastron SDM630Modbus-V3 is a versatile three-phase digital electricity meter designed for accurate measurement of active and reactive power in 1-phase AC (1p2w) as well as 3-phase (3p3w, 3p4w) networks. Its compact design, suitable for 35mm DIN rail mounting, and a wide load range up to 80A make it an ideal solution for various applications, including photovoltaics and e-mobility. This manual provides essential information for the proper installation, operation, and maintenance of your device.

Eastron SDM630Modbus-V3 Digital Electricity Meter

Figure 1: Eastron SDM630Modbus-V3 Digital Electricity Meter

Questa immagine mostra la parte anteriore view of the Eastron SDM630Modbus-V3 meter, showing its LCD display, control buttons, and branding. The display indicates current readings and units.

2. Configurazione e installazione

The SDM630Modbus-V3 is designed for easy snap-on mounting on a standard 35mm DIN rail. Ensure all power is disconnected before beginning installation.

2.1 Montaggio

The meter has a width of 4HP (72mm) and is designed for secure attachment to a 35mm DIN rail. Simply align the meter with the rail and press firmly until it clicks into place.

Eastron SDM630Modbus-V3 Features and Mounting

Figure 2: Key Features and DIN Rail Mounting

This image highlights various features of the meter, including the pulse LED, backlit LCD display, simple touch operation, 4-module width, sealing opening for security, and 35mm DIN rail mounting capability.

2.2 Collegamenti di cablaggio

The meter supports various input configurations:

  • trifase a 3 fili
  • trifase a 3 fili
  • trifase a 1 fili

Refer to the wiring diagram provided with the product for specific connection points. Ensure all connections are secure and comply with local electrical codes. The meter can handle measurements from 20mA up to a maximum of 80A continuous load.

Eastron SDM630Modbus-V3 DIN Rail Meter Features

Figure 3: Meter for DIN Rails - Key Capabilities

This image illustrates the meter's capabilities, including its function as a three-phase multi-function network analyzer, 100A direct load, compatibility with 3P4W/3P3W/1P2W systems, 4-module width, measurement of various parameters (kWh, kVArh, W, Var, VA, PF, Hz, dmd, V, A, THD), bi-directional measurement for kW and kWh, RS485 Modbus RTU, and two pulsed outputs.

3. Istruzioni per l'uso

The SDM630Modbus-V3 features a clear, illuminated display and simple direct operation for viewing various measurement parameters.

3.1 Display e navigazione

The LCD display shows real-time energy consumption and other measured values. Use the navigation buttons (typically 'M' for Menu, 'P' for Page, and arrow keys) to cycle through different display screens and access settings.

3.2 Measurement Options

The meter provides a wide range of measurement data, including:

  • Total Active Energy (kWh)
  • Energia reattiva totale (kVArh)
  • Potenza attiva (kW)
  • Reactive Power (kVArh)
  • Apparent Power (kVA)
  • Fattore di potenza
  • Voltage(V)
  • Corrente (A)
  • Frequenza (Hz)

Active power (kWh) and reactive power (kVArh) are calculated on a net basis, displaying both total counter readings and separate import/export values.

3.3 Interfacce di comunicazione

The meter is equipped with:

  • RS485 Modbus-RTU Interface: For remote reading and integration into energy management systems. Supports communication up to 19.2bps.
  • 2 Pulse Outputs (S0): For import and/or export, useful for connecting to external data loggers or control systems. P1 is fixed at 400 imp/kWh, while P2 is adjustable.

4. Manutenzione

The Eastron SDM630Modbus-V3 is designed for long-term, reliable operation with minimal maintenance. Regular inspection of connections and the meter's physical condition is recommended.

  • Pulizia: Utilizzare un panno morbido e asciutto per pulire l'esterno del misuratore. Non utilizzare detergenti abrasivi o solventi.
  • Connessioni: Controllare periodicamente tutti i collegamenti elettrici per assicurarsi che siano ben saldi e privi di corrosione.
  • Sigillatura: The meter includes a sealing opening for security after installation, protecting against tampering. Ensure this seal remains intact if required for billing or regulatory purposes.

No user-serviceable parts are inside the meter. Refer all internal servicing to qualified personnel.

5. Risoluzione Dei Problemi

If you encounter issues with your Eastron SDM630Modbus-V3 meter, consider the following common problems and solutions:

  • Nessun display/alimentazione:
    • Controllare tutti i collegamenti elettrici per accertarsi che siano sicuri e cablati correttamente.
    • Verificare che il volume di ingressotage is within the specified range (100~280V AC L-N, 100~480V AC L-L).
  • Letture errate:
    • Confirm that the wiring configuration (1-phase, 3-phase 3-wire, 3-phase 4-wire) matches your electrical system.
    • Ensure current transformers (CTs), if used with a different model, are correctly installed and ratio is configured. (Note: This model is direct measuring up to 80A).
    • Check for any external interference or magnetic fields near the meter.
  • Problemi di comunicazione (RS485):
    • Verify the RS485 wiring polarity (A/B).
    • Check Modbus address and baud rate settings on both the meter and the master device.
    • Ensure proper termination resistors are used on the Modbus network if necessary.
  • Pulse Output Not Working:
    • Confirm the pulse output settings (P1 fixed, P2 adjustable) are correct.
    • Check the connection to the receiving device.

If problems persist after attempting these solutions, please contact Eastron technical support or your local distributor for assistance.

For more detailed information on Modbus communication and specific error codes, refer to the comprehensive technical manual available from Eastron.

6. Specifiche

The following table outlines the technical specifications of the Eastron SDM630Modbus-V3 digital electricity meter:

Eastron SDM630Modbus-V3 Specification Table

Figura 4: Tabella delle specifiche dettagliate

This image provides a comprehensive table detailing the electrical, performance, and communication specifications of the Eastron SDM630Modbus-V3 meter, including input voltage, frequency, current range, pulse outputs, Modbus parameters, and environmental conditions.

Eastron SDM630Modbus-V3 Technical Data
ParametroValore
Ingresso volumetage (LN)100~280 V CA
Ingresso volumetage (LL)100~480 V CA
Gamma di frequenzaFrequenza
Intervallo di misurazione corrente20mA to max. 80A continuous load
S0 Pulse Outputs2
S0 Pulse Rate (P1)Fixed at 400 imp/kWh
Comunicazione serialeInterfaccia RS485 MODBUS RTU
Velocità in baudFino a 19.2kbps
Dimensioni (L x P x A)Dimensioni: 10 x 7.2 x 6.6 cm
Peso380 grammi
Montaggio35mm DIN rail (4HP width)
Temperatura di esercizioda -25°C a +55°C
Eastron SDM630Modbus-V3 Dimensions

Figura 5: Dimensioni del prodotto

This image provides a technical drawing of the meter with its dimensions: Height 100mm, Width 72mm, Depth 66mm, and DIN rail depth 35mm.

7. Garanzia e supporto

Eastron products are manufactured to high quality standards. For information regarding warranty coverage, please refer to the warranty card included with your product or visit the official Eastron website. In case of technical issues or inquiries not covered in this manual, please contact Eastron customer support or your authorized dealer. When contacting support, please have your product model number (SDM630-MODBUS-MID V3) and serial number ready.

Documenti correlati - SDM630-MODBUS-MID V3

Preview Manuale utente del contatore intelligente Eastron SDM630-Modbus V2 su guida DIN
Manuale utente completo per il contatore intelligente Eastron SDM630-Modbus V2 DIN Rail, che descrive in dettaglio le sue caratteristiche, specifiche, configurazione e funzionamento per sistemi elettrici monofase e trifase.
Preview Manuale utente Eastron SDM630-Modbus V2: Guida al contatore intelligente su guida DIN
Comprehensive user manual for the Eastron SDM630-Modbus V2 DIN Rail Smart Meter. Learn about its features, measurements, setup, and operation for single and three-phase electrical systems.
Preview Manuale utente del contatore intelligente su guida DIN Eastron SDM630-EV
Manuale utente per il contatore intelligente Eastron SDM630-EV per guida DIN, che descrive in dettaglio caratteristiche, specifiche, installazione e funzionamento per sistemi elettrici monofase e trifase. Include schemi elettrici, dimensioni e specifiche tecniche.
Preview Manuale utente Eastron SDM630-Modbus V2: Guida al contatore intelligente su guida DIN
Comprehensive user manual for the Eastron SDM630-Modbus V2 DIN Rail Smart Meter, detailing its features, specifications, operation, and setup for single and three-phase electrical systems. Includes measurement capabilities, communication protocols (Modbus RTU), and configuration options.
Preview Eastron SDM630-Modbus V3 Smart Meter Installation and Communication Guide
A guide to installing and configuring the Eastron SDM630-Modbus V3 smart meter for communication with inverters, including packaging confirmation, wiring instructions, and communication address settings.
Preview Manuale utente del contatore di energia intelligente Eastron SDM630MCT-MOD-MID
Manuale utente completo per il contatore di energia intelligente Eastron SDM630MCT-MOD-MID DIN Rail, che descrive in dettaglio le sue caratteristiche, specifiche, configurazione e installazione per sistemi elettrici monofase e trifase. Copre la misurazione della tensionetage, current, power, energy, and communication protocols like Modbus RTU.