1. Introduzione
This manual provides detailed instructions for the installation, operation, and maintenance of the QOLTEC 50900 Three Phase Electronic Energy Consumption Meter. This device is designed for measuring active energy consumption in three-phase, four-wire AC circuits. Please read this manual thoroughly before installation and use to ensure proper function and safety.
2. Informazioni sulla sicurezza
AVVERTIMENTO: Installation and maintenance of this device must be performed by qualified personnel only. Failure to follow these instructions can result in electric shock, fire, or serious injury.
- Scollegare sempre l'alimentazione prima di installare o effettuare la manutenzione del contatore.
- Assicurarsi che tutti i collegamenti elettrici siano sicuri e corretti secondo lo schema elettrico.
- Do not operate the meter in environments exceeding its specified operating conditions.
- Do not open or modify the meter casing. All'interno non ci sono parti riparabili dall'utente.
- Protect the meter from moisture, dust, and direct sunlight.
3. Prodotto finitoview
The QOLTEC 50900 is a compact, DIN rail mountable electronic energy meter designed for accurate measurement of three-phase energy consumption. It features an LCD display for clear readings and a pulse output for remote monitoring.

Figure 3.1: QOLTEC 50900 Energy Meter showing dimensions (75mm x 92mm x 76mm) and key features like Three Phase Type, 230V Rated Voltage, 1.0 Precision Class, and LCD Display.
Caratteristiche principali:
- Three-phase, four-wire measurement
- LCD digital display for energy consumption (kWh)
- DIN rail mounting (4P width)
- High accuracy (Class 1.0)
- Pulse output (400imp/kWh)
- Volume di eserciziotage: 3x230/400V
4. Specifiche
| Parametro | Valore |
|---|---|
| Modello | 50900 |
| Volume nominaletage | 3x230/400V AC |
| Corrente nominale | 3x10(100)A |
| Frequenza | 50 Hz |
| Classe di precisione | 1.0 |
| Display | LCD |
| Uscita a impulsi | 400imp / kWh |
| Installazione | DIN Rail (4P) |
| Dimensioni (L x A x P) | Dimensioni: 75 x 92 x 76 mm |
| Peso | 100 grammi |
| Materiale | Acrilico |
5. Configurazione e installazione
The QOLTEC 50900 meter is designed for standard 35mm DIN rail mounting. Ensure the installation location is dry, well-ventilated, and free from excessive vibration or electromagnetic interference.
5.1 Montaggio
- Individuare una guida DIN da 35 mm adatta all'interno del quadro elettrico.
- Align the meter's DIN rail clip with the rail.
- Premere saldamente il misuratore sulla rotaia finché non scatta in posizione.

Figure 5.1: The QOLTEC 50900 meter securely mounted on a DIN rail, showing its compact form factor.
5.2 Collegamenti di cablaggio
IMPORTANTE: All wiring must comply with local electrical codes and regulations. Ensure power is OFF before making any connections.
- Identify the input (IN) and output (OUT) terminals on the meter.
- Connect the incoming three-phase lines (L1, L2, L3) and Neutral (N) to the corresponding IN terminals (typically 5, 6, 7, 8).
- Connect the outgoing three-phase lines (L1, L2, L3) and Neutral (N) to the corresponding OUT terminals (typically 1, 2, 3, 4).
- Assicurarsi che tutti i collegamenti siano ben saldi e sicuri per evitare contatti allentati e surriscaldamento.

Figura 5.2: lato view of the meter showing the wiring diagram for input (IN) and output (OUT) connections for L1, L2, L3, and Neutral.

Figura 5.3: Fronte view of the meter with its LCD display and a separate view del morsetto per i collegamenti elettrici.
6. Istruzioni per l'uso
Once properly installed and powered, the QOLTEC 50900 meter will automatically begin measuring energy consumption.
Display LCD 6.1
The LCD displays the total active energy consumption in kilowatt-hours (kWh). The display is continuous and does not require any button presses for basic reading.

Figura 6.1: primo piano view of the LCD display showing an example energy reading in kWh.
6.2 Uscita a impulsi
The meter features a pulse output (400imp/kWh) which can be used to connect to external monitoring systems for remote data collection. Refer to the external system's documentation for connection details.
7. Manutenzione
The QOLTEC 50900 energy meter is designed for maintenance-free operation under normal conditions.
- Pulizia: Use a soft, dry cloth to clean the meter's exterior. Do not use abrasive cleaners, solvents, or liquids that could enter the casing.
- Ispezione: Periodically inspect the wiring connections for any signs of loosening or damage. Ensure the meter is free from dust accumulation.
- Condizioni ambientali: Per prolungare la durata del misuratore, assicurarsi che l'ambiente operativo rimanga entro gli intervalli di temperatura e umidità specificati.
8. Risoluzione Dei Problemi
If you encounter issues with your QOLTEC 50900 meter, refer to the following common problems and solutions:
| Problema | Possibile causa | Soluzione |
|---|---|---|
| Nessun display/Il misuratore non si accende | No power supply; Incorrect wiring; Blown fuse in circuit | Check power supply to the meter. Verify wiring connections. Check circuit breaker/fuse. |
| Incorrect energy reading | Incorrect wiring; Faulty meter | Verify wiring connections against the diagram. If wiring is correct, contact support. |
| Pulse output not working | Incorrect connection to external system; Faulty meter | Check pulse output wiring to the external system. Consult external system's manual. If issue persists, contact support. |
If the problem persists after attempting these solutions, please contact Qoltec customer support.
9. Garanzia e supporto
Qoltec products are manufactured to high-quality standards. For warranty information and technical support, please refer to the warranty card included with your product or visit the official Qoltec websito. Conserva la ricevuta d'acquisto come prova d'acquisto.